Sms Command Syntax; Sms Command Table - Moxa Technologies ioLogik W5300 Series User Manual

Table of Contents

Advertisement

ioLogik W5300

SMS Command Syntax:

#GetSMS?command_channel=?&command_channel=?...#
#SetSMS?command_channel=X&command_channel=X...#
Details:
1. SMS commands start and end with a "#" sign.
2. Multiple commands can be integrated using an "&" sign.
3. No space or carriage return/linefeed (enter) are allowed between characters.
4. Commands are NOT case sensitive.
5. To query status, use "GetSMS?" after the 1st "#" sign.
a. Use "=?" after a query command (Read, or Read/Write privilege)
6. To control an output, use "SetSMS?" after the 1st "#" sign.
a. Use "=X" after a control command (Read/Write privilege), where X means the actual command
parameters such as 0 (On), 1 (Off), or value (expansion AO channels).
b. The ioLogik will response with the current output status if the commands are received and processed
correctly.
c. Output control is forbidden if the target channel is currently in use by the Click&Go logic. Integrate the
Internal Register function in the Click&Go logic to perform such tasks by controlling the Internal
Registers.
7. The ioLogik will not respond to illegal commands or wrong control parameters.
8. Only the first 140 characters of a response will be kept; the rest will be discarded.
9. SMS message content:
a. Format: ASCII
b. Maximum number characters: 140

SMS Command Table

System Information Commands:
SMS Command
DATE
TIME
IP
WIP
LOC
DESC
FWR_V
MOD_NAME
SN_NUM
MAC_ADDR
EXP_MOD_NUM
EXP_DEV_MOD_TYPE
Example:
1. Query ioLogik W5300 system date:
#GetSMS?DATE=?#
2. Query the ioLogik W5300 Server Location:
#GetSMS?LOC=?#
3. Query the ioLogik W5300 Server Time and LAN IP:
#GetSMS?TIME=?&IP=?#
Attribute
Note
Read
Current Date
Read
Current Time
Read
Current LAN IP address
Read
Current WAN(Cellular) IP address
Read
Server Location
Read
Server Description
Read
Current Firmware Version
Read
Model Name
Read
Serial Number
Read
MAC Address
Read
Number of attached E1200 modules
Read
Expansion ioLogik E1200 Type
DEV=Device slot number, start index:01
B-2
SMS Commands

Advertisement