The Outdoor Unit Power Supply Error - Samsung AQV09VBA Service Manual

Split-type air conditioner
Hide thumbs Also See for AQV09VBA:
Table of Contents

Advertisement

Troubleshooting

12-2-2 The Outdoor unit power supply error

1. Checklist :
1) Are the input power voltage and the power connection correct?
2) Is there no Fuse short in the indoor unit and outdoor unit?
3) Is the cable connected correctly between the indoor unit and outdoor unit in order.
4) Is the wire connected correctly to the terminal block of the indoor unit and outdoor unit?
2. Troubleshooting procedure
Is the voltage of indoor unit
terminal block 1 and 2 correct
after power input?
Pull out the power cord
and execute the following step
after 30 seconds.
Is the outdoor unit normal?
Is the outdoor unit normal?
Is the reactor connected correctly?
Is the +, - of C102 short?
Exchange the PCB.
Is the +,- of C102 short?
Exchange the PCB.
12-3
141 Kinderkamack Rd, Park Ridge, NJ 07656 Tel: 201-782-1782 Fax: 201-782-1783 Web: www.amgair.com Email: info@amgair.com
No
Yes
Is the indoor unit fuse normal?
No
Yes
No
Yes
No
Yes
Yes
No
Yes
No
Is the R701 resistance of
indoor PCB 200Ω?
No
Exchange the fuse.
Connect the reactor wire.
Disassemble the PCB
from the case.
Yes
Is there no error at
the insertion of PCB?
Yes
Exchange the PCB.
Are the BLDC FAN Wire
1 and 3 short?
Yes
Exchange the BLDC FAN.
Air Marketing Group LLC
Exchange the PCB.
Exchange the fuse.
Normal Operation
Exit