Operation Check & Aeration Settings Adjustment; Front, Trim And Barrier Screen Installation - Valor 700IN Owner's Manual

Table of Contents

Advertisement

QUALIFIED
Operation Check & Aeration Settings Adjustment
INSTALLER
Operation Check
Turn the fi replace fl ame up and down using the
remote control to confi rm that the full range of inputs
is achieved—see the remote control operation
instructions on pages 10-15.
Aeration Settings
Light the fi re and allow the unit to warm up for 10–15
minutes to evaluate the fl ame picture. Burners are
equipped with an adjustable shutter to control primary
aeration. See the fi gures below. The shutters are
factory-set to an aeration gap which will give optimum
performance for the vast majority of installations.
Air Shutters
NG Air Shutter
Slider & Cover
Install the front or trim chosen by the customer for their
fi replace. Install as well the barrier screen which is
provided with the front or trim.
Show the customer how to access the controls when
the front or trim are installed and how to remove them.
Follow the instructions provided with the front or trim
and leave those instructions behind for the customer's
further reference.
36
NG
Close
Open
Close
Open

Front, Trim and Barrier Screen Installation

In a few unusual installations, the fl ame picture may
be improved by adjusting the aeration. The need for
adjustment should be determined only by operating the
appliance with the ceramic logs and window installed.
Increasing aeration (open) will cause the fl ames
to appear more transparent and blue showing more
ceramic log glow.
Decreasing aeration (close) will cause the fl ames to
appear more yellow or orange showing less ceramic
log glow.
Too little aeration may result in black carbon
forming and dropping into the fi rebox.
Flashback
shield (for
LPG only)
LPG Air Shutter
Slider
LPG
Close
Open