Selection Chart - Mitsubishi Daiya SRK50HA User Manual

Wall mounted type room air-conditioner, split system, air to air heat pump type
Table of Contents

Advertisement

1.2.5 Selection chart

Correct the cooling and heating capacity in accordance with the conditions as follows. The net cooling and heating capacity can be
obtained in the following way.
Net capacity = Capacity shown on specification
(1) Coefficient of cooling and heating capacity in relation to temperatures
(2) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way piping length between the indoor and outdoor
units.
Piping length [m]
Cooling
Heating
(3) Correction relative to frosting on outdoor heat exchanger during heating
In additions to the foregoing corrections (1), (2) the heating capacity needs to be adjusted also with respect to the frosting on the
outdoor heat exchanger.
Air inlet temperature of
outdoor unit in ˚C WB
Adjustment coefficient
How to obtain the cooling and heating capacity
Example : The net cooling capacity of the model SRK50HA with the piping length of 15m, indoor wet-bulb temperature at 19.0˚C
and outdoor dry-bulb temperature 35˚C is Net cooling capacity =
1.3
1.2
Cooling
1.1
1.0
0.9
0.8
0.7
0.6
43
40
35
30
25
20
15
Indoor air W.B. temperature °C W.B.
27
25
20
15
10
-10
-5
Outdoor air W.B. temperature °C W.B.
7
10
15
1.0
0.99
0.975
1.0
1.0
1.0
-10
-9
0.95
0.94
0.93
Correction factors as follows.
Heating
Applicable range
14
16
18
20
ISO-T1 Standard Condition
0
5
10
ISO-T1 Standard Condition
-7
-5
-3
-1
0.91
0.88
0.86
45000
0.975
SRK50HA
Length 15m
24
22
20
15
1
3
5
0.87
0.92
1.00
1.0
=
4387 w
Factor by air
temperatures