Maintenance
Loosen both sets of retaining clips (fig. 44, pos. 4 and 5)
of the burner cover and remove the burner cover with the
fan unit and the gas burner fitting (fig. 45, pos. 1).
Remove the gas/air distributor plate (fig. 45, pos. 2), the
orifice plate (GB142-24, GB142-30 and GB142-60 only,
fig. 45, pos. 3) and the burner (fig. 45, pos. 4). Note that
the orifice plate of the GB142-60 has a different shape.
Clean the gas/air distributor plate, the orifice plate
(GB142-24, GB142-30 and GB142-60 only) and the
burner using compressed air.
Remove the baffle plate and clean it using compressed
air (fig. 46).
Flush the heat exchanger with water.
Re-assemble all parts in reverse order of disassembly.
NOTICE
It is important to inspect and properly replace
the rubber gaskets.
Switch on the heating system using the main switch.
Press the "Chimney Sweep"
point is displayed. Leave the boiler on for approx.
10 minutes.