7.0 FAULT FINDING
YOUR HEATRAE SADIA MULTIPOINT INSTANTANEOUS SHOULD
GIVE TROUBLE FREE OPERATION. HOWEVER SHOULD A
PROBLEM OCCUR THE TABLE BELOW SHOULD ALLOW MOST
FAULTS TO BE IDENTIFIED. FAULT FINDING SHOULD ONLY BE
CARRIED OUT BY A COMPETENT PERSON.
SYMPTOM
POSSIBLE CAUSE
1. Water too hot
A. Water flow too low
2. Water too cold
A. Electrical power to
B. Water flow too high
C. Element fault
3. Temperature
A. Pressure switch is
varies while
showering,
cycling
hot/cold
B. Input pressure is
4. "Power on"
A. Cartridge fuse or
indicator not lit.
Isolating switch
"ON" but its
neon not lit
B. Residual current
5. Water emerges
A. Expansion relief valve
from expansion
relief valve
6. No water flows
A. Water supply turned
with valve open
B. Unit frozen
For any faults that cannot be identified using the Fault Finding chart
please contact the Heatrae Sadia Service Department, telephone
0844 871 1535, fax 0844 871 1528.
12
the Multipoint heater
is off
operating,
normally making a
"click" as it does so
below 1.0 bar
(14.5psi); flow is
not stable
miniture circuit
breaker (mcb) has
operated in your
fusebox (or
consumer unit) or
switch fuse
device (rcd) or
(earth leakage
circuit breaker)
has operated
has operated
off
REMEDY
Increase the flow by turning the stop valve
Ensure that the electrical supply to the Multipoint
Instantaneous is switched on and the neon is lit
Reduce the flow by adjusting the water control
isolating valve
Check for open circuit
Check water pressure/flow
Ensure that your stop cock and servicing
valve are opened fully
Switch off Multipoint Instantaneous and isolating switch.
Renew fuse, reset the mcb. If they operate
a second time, contact a qualified electrician
Follow the same procedure as above. If this
has happened with a "split load" consumer
unit on initial installation, check that the
neutral core of the Multipoint Instantaneous feed cable
is connected to the "protected" neutral bar of the unit
1. Switch off immediately at isolating switch
2. Turn water off at the servicing valve (if fitted)
or stop valve
3. Contact Heatrae Sadia Service Department
Turn on water supply
Turn OFF ELECTRICITY at isolating switch and
contact installer DO NOT USE THE MULTIPOINT
INSTANTANEOUS