7797 Outside temperature via LON
"Outside temperature 7797"
If several subscribers use the current
outside temperature value, this can be
made available centrally by one device
within a system. All other subscribers in
the same system can receive the tem-
perature values.
Note
Only one subscriber within a system may
transmit the outside temperature.
Valu
Explanation
e
"0"
Device captures the outside tem-
perature via the locally connected
temperature sensor.
"1"
Device captures outside temper-
ature of another LON subscriber
within the same system.
"2"
Device transmits outside temper-
ature. All LON subscribers within
the same system can receive
these values.
77FF Time via LON
"Time 77FF"
Parameter group communication
Delivered condition
Setting range
0
0 to 2
217