Operation
MX-900B Start-up
1. Manually switch "On" Main electrical disconnect switch
2. Verify Emergency Stop palm button is reset (pulled up)
3. On Overview Screen, press the "On/Off" rotary switch icon to
display the Combustion System screen.
4. Press the "Enable" icon on Combustion System screen
Note: if the fuel Metering bin is not full, the Fuel InFeed timer will
count down to zero, and then automatically begin to fill the Metering
Bin.
5. Return to the Overview screen.
6. Press the Gages icon
7. Press the Stack O2 % Bar Graph icon to display the O2 Control
screen.
8. Press the Control Mode "Auto" icon
9. Return to the Overview screen
10. Press the ID Fan icon to display the ID Fan screen
11. Press the "Auto" icon
12. Press the "Start" icon. The ID fan motor will start.
13. Return to Overview Screen
14. Press the Feed Auger icon to go to Feed Auger screen
15. Press the "Auto" icon to enable automatic feed auger control
16. Press the "Start" icon to start the feed auger motor.
Max-Ox™ MX-900B Operators Manual, Rev. 0
Page 29 of 54