Installation

The Max-Ox™ MX-900B Commercial Wood-chip Fired Hydronic Boiler is
a mechanical draft, direct-vented, NON-PRESSURIZED VESSEL, solid
fuel burning appliance. It must be installed in accordance with this Manual,
NFPA 211, Federal, State, and Local codes, and your Insurance
Underwriter's requirements.
Local building code enforcement officials and fire inspectors are given
authority to determine if specific installations of solid fuel burning
appliances are safe. These professionals use recommended guidelines from
various nationally recognized organizations, such as the National Fire
Protection Association (NFPA), and the National Electrical Manufacturer's
Association (NEMA).
Please be sure to follow the requirements of the Authority Having
Jurisdiction over your specific installation.
Your Insurance Underwriter may also have specific guidelines with respect
to installation and inspection requirements for your solid fuel burning
appliance.
The Max-Ox™ MX-900B must be installed per the requirements of National
Fire Protection Association (NFPA) 211: Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel Burning Appliances, 2006 Edition.
Minimum horizontal clearance from combustible materials must be 48
inches in order to permit access door operations during routine maintenance.
Where permissible, additional horizontal clearance is desirable for ease of
maintenance access.
Minimum clearance from the top of the hot water heating boiler to a
combustible ceiling shall be no less than 36 inches. Additional vertical
clearance is desirable, where possible, for ease of maintenance access.
The MX-900B must be placed on a non-combustible concrete surface
designed to support the 7,800 pound shipping weight of the unit, plus an
additional 2,500 pounds for the heat transfer fluid in the hot water heating
boiler.
Max-Ox™ MX-900B Operators Manual, Rev. 0