REHAU STAR TECHNICAL DATA

STAR PUMP RELAY

Boiler and Pump, Logic Module
This is an Intelligent electronic control interface that can switch the
pump and boiler dependant on the requirements of the main wiring
center. This unit is used to protect the boiler and pump and to reduce
cold cycling of the boiler so as to ensure there is a demand for heat
prior to switching on the boiler and pump unit.
Our experience over the years have proved that this reduce excessive
energy usage and ensures better control of the Underfl oor Heating.
The pump module is optional and has the following functions:
-
Pump Overun
It can allow the pump to have a run on time of 3 minutes once
sensors have swiched off if required this function can be de
activated using jumpers shown.
Jumper
Function
J2-Pump overrun time
ON -OFF
ON - After all controller have switched
off the pump runs for an additional 3
minutes for boiler protection
OFF - Disables pump over run. When
all controller are switched off the
pump will also switch off immediately
as well
Technical Data
Article No:
Operating Voltage:
Flexible cable
Solid Cable:
Ambient temperature:
Storage temperature:
Protection Rating:
Current Rating:
Dimensions H/W/D:
Switch contact:
-
Pump and Boiler Delay
This can enable boiler and pump protection, for instance it delays
the turn on time for pump and boiler by three minuites after an
sensor calls for heat if required this function can be de activated
using jumpers shown
Default Setting
Jumper
Jumper is ON (3
J1-Boiler and pump
minute) position
protection ON -OFF
STAR Centre Pump Relay
206577
230V AC
1.0 - 1.5 mm
2
2
0.5 - 1.5 mm
0°C - 50°C
-25°C to + 60°C
IP 20
3(2) A
85mm x 85mm x 38mm
Potential free
Function
ON -Enables boiler and pump protec-
tion (delays turning on pump and boiler
relays for 3 minutes when a controller
calls for heat)
OFF - Disables boiler and pump
protection (immediately turns pump
and boiler relays on when a controller
calls for heat
4.
4.4
Default Setting
Jumper is ON (3
minute) position
13