ELECTRICAL CONNECTIONS
DANGER
Disconnect power before servicing the product.
Failure to do so could result in death or
electrical shock.

General information

WARNING
x The DECT series models may be powered
at 240V or 208V.
This cooktop does not require a neutral connection. If
the cooktop is to be completely enclosed in a cabinet,
feed the cooktop cable through the opening in the
cabinet. Make the electrical connection following the
appropriate steps for your installation.
Your cooktop must be connected to the proper
electrical voltage and frequency as specified in the
table on the right.
Figure 12. Location of serial tag
Connect with copper wire only
If the house has aluminum wiring, follow the
procedure below:
1. Connect the aluminum wiring to the copper wire
by using special connectors designed and
Underwriters Laboratories-listed for joining copper
to aluminum. Follow the electrical connector
manufacturer's recommended procedure.
2. Aluminum/copper connection must conform with
local codes and industry- accepted wiring
practices.
Electrical Connections
The flexible conduit (supplied) 4 feet long (123 cm)
located at the right rear of the cooktop bottom box
should be connected directly to junction box. Do not
cut or lengthen the conduit. A U.L - or CSA - listed
conduit connector must be provided at each end of the
power supply cable (at the cooktop and at the junction
box.) A time delay fuse or circuit breaker is
recommended. Do not ground to a gas pipe.
Do not have a fuse in the grounding or neutral circuit.
Fuse both supply (phase) lines.
Improper connection of aluminum house wiring to
the copper leads can result in a serious problem.
30"
30"
36"
36"
Batter/march Park Quincy, Massachusetts 02269
A three-wire, single phase, 240 Volt 60 cycle electrical
system (properly circuit protected to meet Local
Codes of NFPA No.70) must be provided. Unit must
be properly grounded in accordance with local wiring
code. The chart below recommends the minimum
circuit protector and wire size if the appliance is the
only unit on the circuit. If smaller sizes of wire are
used, the unit efficiency will be reduced and a fire
hazard may be created. It is advisable that the
electrical wiring and hookup be accomplished by a
competent electrician.
9
WARNING
Power Supply
Model
Power Supply
240 V 60 Hz
Model
240 V 60 Hz
ECCB330H1ASS
6,7kW
28A
DECT304
6,7kW
28A
ECCB330H1ABL
DECT365
9,4kW
39A
ECCB336H1ASS
9,4kW
39A
ECCB336H1ABL
National Fire Protection Association
ENGLISH
Approval
208 V 60 Hz
code
Approval
208 V 60 Hz
code
514T40IA
5,03kW
24A
5,03kW
24A
514T40NA
514T40NA
7,06kW
34A
514V50NC
514V50IC
7,06kW
34A
514V50NC