Installing The Gasline; Installing The Remote Switch; Vent Requirements - Montigo M38BV-ST See-Thru Installation Operation & Maintenance

B-vented gas fireplace
Hide thumbs Also See for M38BV-ST See-Thru:
Table of Contents

Advertisement

M38BV-ST B-Vented Fireplace
Installing The Gas Line
The gas line must be installed before finishing the M38BV-ST
fireplace. Natural Gas requires a minimum inlet gas supply pressure
of 5.5" W.C. & a manifold pressure of 3.5" W.C. Propane Gas
requires a minimum inlet gas supply pressure of 11" W.C. & a
manifold pressure of 10" W.C. Provision must also be made for a 1/8"
N.P.T. plugged tapping and be accessible for test gauge connection
immediately upstream of the gas supply controls to the appliance.
The fireplace gas connection and the main operating gas valve is
located behind the removable brass trim at the bottom of the unit and
need only be attached to the gas line with an approved fitting, as
required by the applicable installation codes.
1 3/4
2 3/8
7
1 3/4
Figure 3. Gas line access.
The appliance and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shutoff valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
* After gas line is connected each appliance connection,
valve and valve train must be checked while under normal
operating pressure with either a liquid solution, or leak
detection device, to locate any source of leak. Tighten any
areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected. Do
NOT use a flame of any kind to test for leaks.

Installing The Remote Switch

The M38BV-ST is equipped with a remote-operated valve, located
behind the removable brass grille, to the right of the gas control valve
(refer to Figure 10.) The valve is pre-wired and completely self
contained to generate its own power. DO NOT connect any external
power to it.
Note: The switch location must not exceed 30' from the fireplace.
Page 4
Installation
7
B-Vent Installation
The M38BV-ST is certified for use with standard 4" B-Vent and
requires no B-Vent appliance connector. Simply attach the B-Vent to
the fireplace flue collar, and secure it using 1/4" sheet metal screws.
Do not penetrate the inner sleave of the B-Vent when tightening the
screws.
Refer to the current CAN/CGA B-149.1 and .2 or ANSI Z223.1-1988
Gas Installation Code for specific vent sizing.
CAUTION:
Test your B-Vent installation after completion to ensure that
no combustible by-products are spilling from the fireplace
opening. This draft test should be performed after a three(3)
minute warm up period. The manufacturer will not be
responsible for any installations with inadequate draw.
Installation In
Bedrooms and Bedsitting Rooms:
Bedr
Bedr
Bedr
Bedr
ooms and Bedsitting Rooms:
ooms and Bedsitting Rooms:
ooms and Bedsitting Rooms:
ooms and Bedsitting Rooms:
This fireplace is supplied with a secondary limit switch -- an added
safety feature that prevents overheating. This switch will also shut
the fireplace down if the flue becomes blocked. Once the reason for
the shutdown has been cured, the pilot burner must be relit.
XG0400 05/00