10. Additional refrigerant charge

At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and
additional charging of each refrigerant line will be required on site. In order that
future servicing may be properly provided, always keep a record of the size and
length of each refrigerant line and the amount of additional charge by writing it in
the space provided on the outdoor unit.
<Additional charge>
High-pressure
Additional refrigerant
pipe size
charge
Total length of ø28.58
=
×0.36
(kg)
(m)×0.36(kg/m)
Liquid Piping Size
Liquid Piping Size
Total length of ø12.7
Total length of ø9.52
+
+
×0.12
×0.06
(m)×0.12(kg/m)
(m)×0.06(kg/m)
BC controller
Total Outdoor Unit
(Standard/Main)
Model Name
Per Unit
+
(E)P200
2.0kg
(E)P250~(E)P500
3.0kg
(E)P550~(E)P900
5.0kg
<Example>
Indoor
1: 80
A: ø28.58
40 m
2: 250 B: ø9.52
10 m
3: 32
C: ø9.52
20 m
4: 40
D: ø9.52
5 m
5: 32
E: ø9.52
5 m
6: 63
F: ø22.2
3 m
G: ø19.05
1 m
Outdoor
P550
Limitation of the amount of refrigerant to be charged
The above calculation result of the amount of refrigerant to be charged must become below the value in the table below.
Outdoor unit model
P200
P250
Maximum amount of
24.8kg
33.8kg
refrigerant *1 kg
Outdoor unit model
EP200
EP250
Maximum amount of
27.3kg
34.0kg
refrigerant *1 kg
*1 Amount of additional refrigerant to be charged on site
High-pressure
pipe size
Total length of ø22.2
Total length of ø19.05
+
+
×0.23
(m)×0.23(kg/m)
Liquid Piping Size
Total length of ø6.35
+
×0.024
(m)×0.024(kg/m)
BC controller
(Main) HA-type
+
+
2.0 kg
a: ø9.52
10 m
b: ø9.52
5 m
c: ø6.35
5 m
At the
d: ø6.35
10 m
conditions
e: ø6.35
5 m
below:
f: ø9.52
5 m
P300
P350
P400
P450
34.8kg
39.7kg
46.7kg
53.7kg
EP300
EP350
EP400
EP450
35.0kg
39.7kg
47.5kg
49.2kg
10.1. Calculation of additional refrigerant
charge
Calculate the amount of additional charge based on the length of the piping
extension and the size of the refrigerant line.
Use the table below as a guide for calculating the amount of additional
charging and then charge the system accordingly.
If the calculation results in a fraction of less than 0.1 kg, round up to the next
0.1 kg. For example, if the result of the calculation was 30.73 kg, round the
result up to 30.8 kg.
High-pressure
High-pressure
pipe size
pipe size
Total length of ø15.88
+
×0.16
×0.11
(m)×0.16(kg/m)
(m)×0.11(kg/m)
BC controller
BC controller
(Sub) Total Units
(Sub) Per Unit
1
1.0 kg
2
2.0 kg
The total length of each liquid line is as follows:
ø28.58: A = 40 m
ø22.2: F = 3 m
ø19.05: G = 1 m
ø9.52: C + D + E + a + b + f = 50 m
ø6.35: c + d + e = 20 m
Therefore,
<Calculation example>
Additional refrigerant charge
= 40 × 0.36 + 3 × 0.23 + 1 × 0.16 + 50 × 0.06 + 20 × 0.024 + 5 + 2 + 5
= 30.8 kg
P500
P550
P600
P650
60.2kg
69.2kg
72.9kg
74.6kg
EP500
EP550
EP600
EP650
62.9kg
69.6kg
73.3kg
74.8kg
Liquid Piping Size
Total length of ø15.88
+
×0.2
(m)×0.2(kg/m)
Total Capacity of
Per Indoor
Connected Indoor Units
Unit
~80
2.0kg
+
81~160
2.5kg
161~330
3.0kg
331~390
3.5kg
391~480
4.5kg
481~630
5.0kg
631~710
6.0kg
711~800
8.0kg
801~890
9.0kg
891~1070
10.0kg
1071~1250
12.0kg
1251~
14.0kg
P700
P750
P800
P850
90.3kg
91.5kg
91.5kg
91.5kg
EP700
74.8kg
P900
91.5kg
17