Factory-Built Fireplace Requirements, cont'd.
The use of the cast iron surround panels may not
be possible in these instances. A custom-built
surround panel system may be used provided it
does not interfere with air circulation through the
convection chamber/ louvers.
• Air flow within and around the factory-built
fireplace shall not be altered by installation of the
insert.
• Alteration of the fireplace in any manner is not
permitted; i.e. firebrick or refractory panels MUST
NOT be removed in order to accommodate the
insert. Exceptions to this are:
a.
External trim pieces, that do not affect the
function of the fireplace, may be removed
providing they can be stored on or within
the fireplace for reassembly if the insert
were to be removed.
b.
The chimney damper may be removed to
install the chimney liner.
• Inserts that project from the factory-built fireplace
must be furnished with appropriate means of
support. The weight of the insert must not com-
promise the means of support for the factory-built
fireplace.
• Fireplace Conversion Notice 220508 must be per-
manently attached to the back of the fireplace. This
metal label is included in the bag containing this
manual.
• Final approval is contingent on the authority hav-
ing local jurisdiction.
14 7/8" U.S.
18 7/8" CAN
Combustible
from sur-
Flooring
round face
Figure 4. Required hearth protection if flush with
combustible floor materials.
8
10/2/14
Min.
16" U.S.
20" CAN
from door
opening
Min.
Hearth Protection Requirements
The floor area in front of fireplace insert must be
protected from live sparks and radiant heat.
• Materials: Hearth protection must be non com-
bustible insulating board such as 1/2" millboard, or
the equivalent mortared masonry material. Alter-
nate protection must be composed of materials as
specified by NFPA 211.
• Protected Area:
U.S: 16" Deep x 37" Wide
CAN: 20" Deep x 37" Wide
See exception for 18" depth below.
U.S. : Front -
The protection must extend at least 16 inches
forward from the fireplace insert door opening as
in fig. 4. (14 7/8" from Surround facing).
Canada: Front -
The protection must extend at least 20 in. forward
from the fireplace insert door opening, (18 7/8"
from Surround facing).
Front protection may be reduced to 18" under the
following conditions:
a) it is composed of noncombustible material
having an R value of .5 or higher such as 1/2" thick
millboard. See Appendix A on page 23 for exam-
ples.
b) it is raised a minimum of 2 1/2" and constructed
on noncombustible materials in a code-approved
masonry fireplace. See fig. 5.
U.S. & Canada: Sides - Protection must extend a
minimum 18 1/2 in. to both sides of the centerline
of the insert. See fig 6, A.
Min.
18" from
door
opening
2 1/2"
Figure 5. Canada only:
Minimum depth with code-approved raised hearth.