DSC PowerSeries PC1616 Installation Manual page 17

Version 4.2 na security system
Hide thumbs Also See for PowerSeries PC1616:
Table of Contents

Advertisement

[5]
ON: the keypad buzzer follows the bell output for all alarms. OFF: the system only activates the bell output for all alarms.
[6]
ON: When an alarm is detected on a zone (with the Cross Zone attribute enabled), a timer is started. The alarm is not transmitted and
the bell output is not activated unless a second cross zone enabled zone is violated before the Cross Zone timer times out. OFF: the
system reports all alarms normally and logs and transmits a Police Code reporting code if a second zone alarm is detected during the
armed period.
[7]
ON: The system restarts the Exit Delay (one time) if a Delay zone is violated and restored during the exit delay time. OFF: exit
delay does not restart.
[8]
ON: The system activates the trouble beeps when an AC trouble is detected. OFF: the system does not annunciate AC troubles
using the keypad buzzer.
Section [019] Seventh System Option Code
Option
Description
[1]
For Future Use
[2]
ON: Trouble light latches on OFF: Trouble light turns off after restore.
[3]
ON: When disarming, the keypad will display only the first alarm to occur during the last arming period OFF: When disarming,
the keypad will display all zones that were in alarm during the last arming period
[4]-[5]
For Future Use
[6]
ON: the green LED indicator on the keypads indicate the status of AC on the system OFF: the green LED indicator on the keypads
indicate the partition ready status
[7]
ON: All user access codes can enter the User Functions menu. OFF: Only the Master Code can enter the User Functions menu.
[8]
For Future Use
Section [020] Keypad Zone Assignment
Enter the two-digit zone number to be assigned to each keypad assigned to a specific slot. Only one keypad can be assigned to a specific slot.
See Keypad Assignment. Valid entries are from [00] to [64].
Section [021] Eighth System Option Code
Option
Description
[1]
ON: Access codes will not be accepted by the system during entry delay. OFF: An access code can be used to disarm the system
during entry delay
[2]-[5]
For Future Use
[6]
ON: Key-switches and wireless can only disarm the system during an entry delay OFF: Key-switches and wireless keys can
disarm the system regardless if entry delay is active or not.
[7]-[8]
For Future Use
Section [022] Ninth System Option Code
Option
Description
[1]
ON: An access code is required for access to the [ ][1], [ ][2], [ ][3] menus. OFF: No access code is required for [ ][1], [ ][2],
[ ][3] menu access.
[2]-[3]
For Future Use
[4]
ON: Only the Master code can be used to bypass a hold up zone. OFF: Any valid access code can bypass a hold up zone.
WWW.DIYALARMFORUM.COM
Section 4 – Programming Descriptions
15