Evaporator Fan Performance 20 Tons Tc*241C Standard Or Txv Refrigeration System Downflow Or Horizontal - Trane Voyager TC* User Manual

Packaged cooling & gas/electric rooftops 12 1/2-25 tons — 60 hz
Table of Contents

Advertisement

Table 44.

Evaporator Fan Performance 20 Tons TC*241C Standard or TXV Refrigeration System Downflow or Horizontal

.10
.20
CFM
RPM
BHP
RPM
BHP
5-HP Standard Motor & Field Supplied Extra Low Static Drive
4000*
5200*
426
0.94
463
1.09
6400
506
1.64
540
1.84
7200
560
2.28
592
2.50
8000
616
3.07
645
3.31
8800
671
4.04
698
4.29
9600
728
5.19
753
5.46
5-HP Standard Motor & Drive
Continued
1.10
1.20
CFM
RPM
BHP
RPM
BHP
5-HP Standard Motor & Drive
4000*
688
1.87
714
2.03
5200*
722
2.54
747
2.73
6400
765
3.49
788
3.70
7200
799
4.31
820
4.53
8000
837
5.26
857
5.51
8800
879
6.43
897
6.67
9600
925
7.83
941
8.07
For Standard Evaporator Fan Speed (RPM), reference
For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference
For Oversized Evaporator Fan Speed (RPM), reference
Fan motor heat (MBH) = 3.15 x Fan BHP.
Notes:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
Refer to
Table 54
to determine additional static pressure drop due to other options/accessories.
Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product's warranty will not be affected.
*For 4000 and 5200 CFM, unit applications below 320 CFM/Ton are only applicable to TCD models only (No Gas Heat). See below for restrictions.
Electric heaters restricted on applications below 320 CFM/Ton.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters are required on applications below 320 CFM/Ton.
(i)
Field Supplied Fan Sheave B5V200 and Field Supplied Motor Sheave 1VP34 Required. Field Supplied Belt may be necessary.
(ii)
Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
(iii)
7.5 Standard Motor with Field Supplied Motor Sheave IVP50 required. Field Supplied Belt may be necessary.
62
Performance Data
External Static Pressure (Inches of Water)
.30
.40
.50
RPM
BHP
RPM
BHP
RPM
428
0.69
467
0.82
504
494
1.22
524
1.35
555
570
2.03
595
2.19
620
620
2.72
646
2.92
668
672
3.56
696
3.80
719
724
4.55
747
4.83
769
776
5.74
799
6.04
820
7.5-HP Standard Motor w/Field Supplied
Motor Sheave
External Static Pressure (Inches of Water)
1.30
1.40
1.50
RPM
BHP
RPM
BHP
RPM
739
2.20
764
2.36
787
771
2.93
795
3.14
817
810
3.91
832
4.12
854
841
4.76
862
4.99
883
876
5.76
896
6.01
915
915
6.93
933
7.19
951
958
8.32
974
8.58
7.5-HP Oversized Motor & Drive
Table
50.
Table
53.
.60
.70
BHP
RPM
BHP
RPM
BHP
(i)
5-HP Standard Motor & Field Supplied Low Static Drive
0.95
538
1.08
572
1.23
1.51
585
1.67
614
1.83
2.34
644
2.51
669
2.69
3.10
690
3.27
711
3.45
4.02
739
4.22
759
4.41
5.10
790
5.34
808
5.56
6.34
840
6.63
859
6.90
(iii)
1.60
1.70
BHP
RPM
BHP
RPM
BHP
5-HP Standard Motor & High Static Drive Accessory
2.53
810
2.70
831
2.87
3.35
839
3.56
861
3.77
4.34
875
4.57
896
4.80
5.22
902
5.46
922
5.69
6.26
934
6.52
953
6.77
7.46
969
7.74
986
8.01
Table
51.
(20 Tons High Efficiency)
.80
.90
RPM
BHP
RPM
BHP
RPM
(ii)
603
1.38
632
1.55
660
642
2.00
670
2.17
696
693
2.89
717
3.09
741
733
3.65
755
3.86
777
778
4.60
797
4.81
817
826
5.77
844
5.98
861
876
7.14
893
7.37
909
7.5-HP Oversized Motor & Drive
1.80
1.90
RPM
BHP
RPM
BHP
RPM
852
3.05
873
3.23
892
882
3.98
902
4.19
923
916
5.04
936
5.29
955
942
5.94
961
6.19
980
971
7.03
989
7.29
RT-PRC024-EN
1.00
BHP
1.71
2.35
3.29
4.08
5.03
6.20
7.59
2.00
BHP
3.41
4.41
5.54
6.44