Optional Installation Parts - Toshiba RAV-SM2244AT8-A Service Manual

Split type air conditioner
Table of Contents

Advertisement

Digital Inverter
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support the
bottom surface of the fixing leg that is in contact with
and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with
downward piping, consider the piping work.
GOOD
Absorb vibration
with vibration-proof
Fixing leg
rubber pads
Foundation
GOOD
Bottom plate
of outdoor unit
Foundation
Support the bottom surface of
the fixing leg that is in contact
with and underneath the bottom
plate of the outdoor unit.
NO GOOD
If only the
Do not
end of the
support the
fixing leg is
outdoor unit
supported, it
only with the
may deform.
fixing leg.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
15 or less
• When water is to be drained through the drain hose,
attach the following drain nipple and waterproof rubber
cap, and use the drain hose (Inner diam: 16 mm) sold
on the market. Also seal the knockout hole and screws
securely with silicone material, etc., to prevent water
from leaking.
Some conditions may cause dewing or dripping of
water.
EN-11
• When collectively draining discharged water
completely, use a drain pan.
Waterproof rubber cap
Drain nipple
• Please pay attention to the drain in region with
snowfall and cold temperature, as it may be frozen
and cause drainage problems. Punch the knockout
holes on the base plate to improve drainability. Use a
screwdriver and take off the knockout part outward.
Knockout hole
Waterproof
rubber cap
Drain nipple
For Reference
If a heating operation is to be continuously performed for
a long time under the condition that the outdoor
temperature is 0 °C or lower, draining defrosted water
may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally in order to safely install the air conditioner.
For details, contact the dealer.
5
REFRIGERANT PIPING
Knockout of Pipe Cover
Knockout procedure
Rear direction
Front direction
Down direction
• The indoor/outdoor connecting pipes can be
connected in 4 directions.
Take off the knockout part of the pipe cover through
which pipes or wires will pass through the base plate.
• Detach the pipe cover and tap on the knockout section
a few times with the shank of a screwdriver.
A knockout hole can easily be punched.
• As shown in the figure below, it is easier to punch out
the knockout hole when the pipe cover is left in place
rather than when the cover is removed from the unit.
In knocking out the hole, the knockout section can
easily be removed by hand once the bottom of the
three locations where the section is joined along the
guide lines is broken using a screwdriver.
• After punching out the knockout hole, remove burrs
from the hole, and install the protective bush and
guard material around the passage hole provided as
accessories in order to protect the wires and pipes.
Also be sure to attach the pipe covers after connecting
the pipes. The pipe covers can be easily attached by
cutting off the slits at the lower part of the covers.
6
* Be sure to wear heavy work gloves while working.

Optional Installation Parts

(Locally procured)
Pipe cover
Side direction
Parts name
Refrigerant piping
Liquid side: Ø12.7 mm
A
Gas side: Ø19.1 mm
(Approx. 800 mm)
Ø28.6 mm
Pipe insulating material
B
(polyethylene foam, 10 mm thick)
C
Putty, PVC tape
REQUIREMENT
Follow the instructions in the installation manual
provided with the branch pipe kit and the instructions in
the installation manual of the indoor unit to connect the
refrigerant pipe between the branch pipe and indoor unit.
Installation Manual
Q'ty
One each
1
One each
EN-12