2)
Consider the wind direction during the operational
season of the air conditioner, and install the unit
so that the discharge port is set at a right angle
relative to the wind direction.
Strong wind
Strong wind
• When using an air conditioner under low outside
temperature conditions (Outside temp:-5 °C or
lower) in COOL mode, prepare a duct or wind shield
so that it is not affected by the wind.
<Example>
Wind shield
Wind shield
Necessary Space for Installation
(Unit: mm)
Obstacle at rear side
Upper side is free
1.
Single unit installation
EN-9
2.
Obstacles on both right and left sides
The height of the
obstacle should
be lower than
the height of the
outdoor unit.
150 or
250 or
more
more
3.
Serial installation of two or more units
150 or
250 or
250 or
250 or
more
more
more
more
The height of the obstacle should be
lower than the height of the outdoor unit.
Obstacle also above unit
150 or
more
Obstacle in front
Above unit is free
1.
Single unit installation
5
2.
Serial installation of two or more units
Obstacle also at the above unit
1,000 or
more
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1.
Single unit installation
2.
Serial installation of two or more units
250 or
200 or
more
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
1,000 or
300 or
1,500 or
more
more
more

Installation of Outdoor Unit

• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: M10 x 4 pairs)
150
600
Drain
hole
Knockout
hole
Drain nipple mounting hole
more
Installation Manual
2,000 or
200 or
more
more
150
430
EN-10