COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
INDOOR COIL MODEL NO.
CONDENSER
ENTERING AIR
TEMPERATURE
65
75
85
95
105
115
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
Air Handler
Coil
N1AHD2046
G2FD060(S,H)24
F2FP060
G1FA060S21,24
G1FA060S21,24
G1UA060S21,24
Unitary Products Group
EABA-(T,W)060S)
G2FD060(S,H)24
ID CFM
1600
ID DB (°F)
85
80
ID WB (°F)
71
67
T.C.
63.0
61.1
S.C.
39.6
39.7
KW
3.71
3.66
T.C.
62.3
59.8
S.C.
39.6
39.3
KW
4.20
4.14
T.C.
61.7
58.5
S.C.
39.6
38.9
KW
4.70
4.63
T.C.
61.0
57.2
S.C.
39.6
38.5
KW
5.19
5.11
T.C.
58.3
53.9
S.C.
38.5
37.2
KW
5.78
5.67
T.C.
55.5
50.5
S.C.
37.4
35.9
KW
6.36
6.22
T.C.
S.C.
KW
1.00
1.00
1.00
0.98
0.98
1.02
1.00
1.00
1.00
1.00
1.00
1.00
1800
75
85
80
63
71
67
60.7
62.9
60.9
40.3
41.6
41.5
3.68
3.71
3.66
57.9
62.5
60.0
39.1
41.8
41.3
4.12
4.21
4.15
55.1
62.0
59.1
38.0
41.9
41.1
4.57
4.71
4.64
52.3
61.5
58.2
36.8
42.0
40.9
5.01
5.21
5.13
49.1
59.1
54.7
35.4
41.0
39.6
5.55
5.80
5.69
45.9
56.8
51.3
34.0
40.1
38.2
6.08
6.39
6.25
036-21318-002 Rev. A (0106)
2000
75
85
80
63
71
67
61.1
62.9
60.6
42.2
43.7
43.3
3.67
3.71
3.67
58.5
62.6
60.1
41.1
43.9
43.3
4.13
4.21
4.16
55.9
62.3
59.6
40.1
44.2
43.3
4.58
4.72
4.65
53.3
62.0
59.1
39.0
44.4
43.3
5.04
5.22
5.14
49.9
60.0
55.6
37.6
43.6
41.9
5.57
5.82
5.71
46.5
58.0
52.1
36.2
42.7
40.5
6.11
6.41
6.27
75
63
61.4
44.1
3.67
59.0
43.1
4.13
56.6
42.2
4.60
54.2
41.2
5.06
50.7
39.8
5.60
47.1
38.3
6.13