DESCRIPTION

YORK has combined the latest concepts in modern technology
with time-proven quality standards to design a split-system
heat pump to meet the demands of the energy-and
quality-conscious commercial market.
Both the outdoor and indoor units are completely piped and
wired at the factory. Only the interconnecting liquid and vapor
lines are required to complete the refrigerant circuit. Every unit
is dehydrated, evacuated, leak tested and pressure tested
before being pressurized with a holding charge of
refrigerant-22 for shipment and/or storage. The compressor,
the fan motors and the controls are functionally tested after the
units are fabricated to assure a reliable start-up and years of
dependable operation.
These units have been tested by Underwriters' Laboratories
and will be shipped with UL and CUL labels.
OUTDOOR UNIT
Every outdoor unit includes a heavy-duty compressor with a
crankcase heater, line break overload protection, a suction line
accumulator with a fusible plug, a 4-way reversing valve with
a 24-volt solenoid, outdoor fan motor(s) with inherent
protection, and a copper tube/aluminum fin coil that is
positioned vertically for better drainage of the water that will
condense on it during the heating cycle.
They also include a filter-drier, an expansion valve and a
distributor that are only used during the heating cycle plus a
check valve to provide the proper flow of refrigerant through the
unit during both the cooling and heating cycles.
SPLIT-SYSTEM
HEAT PUMPS
50 AND 60 HZ
E2FB090/E1FB120/F3EH090 & 120
7-1/2 & 10 NOMINAL TONS (60 HZ)
7 & 9 NOMINAL TONS (50 HZ)
(9.0 - 9.2 EER)
208/230/460
VOLT ONLY
To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel. After
fabrication, each part is thoroughly cleaned to remove any
grease or dirt from its surfaces. The parts that will be exposed
to the weather are then coated with a "desert sand" powder
paint to assure a quality finish for many years. This coating
system has passed the 750 hour, salt spray test per ASTM
Standard B117. To assist in servicing, the high and low pressure
service connections are exterior to the cabinet, allowing simple
access.
The fan guards are vinyl-coated to provide additional rust
protection. An optional decorative coil guard is available to
protect the coil on the outdoor unit.
INDOOR UNIT
Every indoor unit includes a well-insulated cabinet, a copper
tube/aluminum fin coil, 1" throwaway filters, a centrifugal
blower, a blower motor, adjustable drive components, a blower
motor contactor and a small holding charge of refrigerant-22.
They also include a filter-drier, an expansion valve and a
distributor that are only used during the cooling cycle plus a
check valve to provide the proper flow of refrigerant through the
coil during both the cooling and heating cycles.
The units are shipped in the vertical position ready for field
installation. For horizontal installation, interchange the solid
bottom panel and the return air duct flange on the front of the
unit.
515.41-TG1Y (498)
208/230
VOLT ONLY

Advertisement

Table of Contents
loading

Summary of Contents for York E2FB090

  • Page 1: Description

    VOLT ONLY DESCRIPTION To eliminate the costly cabinet deterioration problems usually YORK has combined the latest concepts in modern technology with time-proven quality standards to design a split-system associated with outdoor equipment, all sheet metal parts are heat pump to meet the demands of the energy-and constructed of commercial grade (G90) galvanized steel.
  • Page 2: Table Of Contents

    515.41-TG1Y APPLICATION FLEXIBILITY OUTDOOR UNITS - EFB090 & 120 These outdoor units are lightweight and can be installed on almost any roof. 7-1/2 TON UNIT SHOWN 5 FT. MIN. Units can be lifted using nylon straps with hooks at the holes provided in the base rails, or they may be lifted with a forklift through the slotted openings in the base rails.
  • Page 3: Ari Ratings

    Heating Capacity Model Cooling Capacity High Outdoor Low Outdoor Temperature (47°F) Temperature (17°F) Outdoor Indoor Unit Unit E2FB090 F3EH090 2.08 E1FB120 F3EH120 Sound Rating Outdoor Unit (bels) E2FB090 E1FB120 1Ratings are in accordance with ARI Standard 240. 2Sound ratings are in accordance with ARI Standard 270.
  • Page 4: Cooling Capacities

    Power Total Sens. Power Total Sens. Power Input Input Input Input Input Input E2FB090/F3EH090 @ 3300 Supply Air CFM - 60 HZ E1FB120/F3EH120 @ 4000 Supply Air CFM - 60 HZ 90.6 86.5 83.1 122.1 116.1 105.4 81.1 77.4 74.2 107.8...
  • Page 5: Heating Capacities (Heat Pump Only)

    515.41-TG1Y HEATING CAPACITIES HEAT PUMP ONLY Temperature of Outdoor Air, °F DB Temperature Air on Indoor Coil, °F DB E2FB090/F3EH090 @ 3300 Supply Air CFM - 60 HZ 27.8 4.06 43.70 6.19 54.10 6.31 63.10 6.63 75.10 6.88 87.60 7.27 96.70...
  • Page 6: Blower Motor And Drive Data

    515.41-TG1Y BLOWER MOTOR AND DRIVE DATA Adjustable Motor Pulley Fixed Blower Pulley Belt Indoor Motor* Blower Unit Pitch Diameter, Bore, Pitch Diameter, Bore, Pitch Length, Designation Model (in.) (in.) (in.) (in.) (in.) FEH090 1-1/2 655-880 2.8 - 3.8 37.3 FEH120 700-950 •...
  • Page 7: Static Resistances

    515.41-TG1Y STATIC RESISTANCES FOR UNIT ACCESSORIES (IWG) Unit Model Accessory 2400 2700 3000 3300 3600 10 KW 0.01 0.01 0.01 0.02 0.02 16 KW 0.01 0.02 0.02 0.03 0.04 ELECTRIC HEAT 26 KW 0.03 0.04 0.05 0.06 0.07 FEH090 36 KW 0.05 0.07 0.08...
  • Page 8: Dimensions And Clearances (Outdoor Units)

    515.41-TG1Y UNIT DIMENSIONS & CLEARANCES - OUTDOOR UNITS EFB090 (7-1/2 Ton) CLEARANCES Overhead (Top) 120" Front 30" (Piping and Access Panels) Left Side 24" Right Side 24" Rear 24" Bottom 0" 1Units must be installed oudoors. Overhanging structures or shrubs should not obstruct air discharge outlet.
  • Page 9: Dimensions And Clearances (Indoor Units)

    515.41-TG1Y UNIT DIMENSIONS & CLEARANCES - INDOOR UNITS ACCESSORIES • ELECTRIC HEATER - Add 14-1/4" to unit height when used. • SUPPLY AIR PLENUM - Add 27-1/2": to unit height when used. • BASE - Add 20" to unit height when used. MINIMUM CLEARANCES Side with RETURN AIR opening 24"...
  • Page 10: Accessory Dimensions

    515.41-TG1Y ACCESSORY DIMENSIONS Nom-KW Model Number 2HS04501025, 46, 50 2HS04501625, 46, 50 2HS04502625, 46, 50 2HS04503625, 46, 50 Unitary Products Group...
  • Page 11: Physical Data

    515.41-TG1Y PHYSICAL DATA (OUTDOOR UNIT) UNIT MODEL DESCRIPTION E2FB090 E1FB120 Compressor Rating - tons 7-1/2 Quantity Fans Diameter - inches No. of Blades/ 24 / 4 22 / 3 Nominal CFM 6000 7600 Fan Motors 1100 1100 Rows Deep x Rows High...
  • Page 12: Electrical Data

    Based on a 3% voltage drop. Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 515.41 TG1Y Subject to change without notice. Printed in U.S.A. Supersedes: 515-41-TG1Y(297) Copyright © by York International Corporation 1997. All Rights Reserved. Code: EBY, EGY, EBI...