Control units
(cont.)
Functions when operating with Vitodata 300:
For all heating circuits in a heating system:
■ Remote monitoring:
– Forwarding messages via SMS to mobile phone/smartphone, per
email to terminal devices with email client function or via fax to fax
machines.
– Monitoring additional devices via the inputs and output of the
Vitocom 200.
■ Remote control:
Adjusting operating programs, set values, time programs and heat-
ing curves.
■ Remote setup:
– Configuring the Vitocom 200 parameters.
– Remote setup of Vitotronic control parameters via coding
addresses.
Note
■ Alongside the data transfer telecommunication costs, usage
charges have to be taken into account for Vitodata 300.
■ For more information, see www.vitodata.info.
Configuration
Type LAN2
■ With dynamic IP addressing (DHCP) the Vitocom 200 is configured
automatically. The DSL router requires no separate settings.
Observe the network settings of the DSL router.
■ The inputs of the Vitocom 200 are configured using the
Vitodata 100 or Vitodata 300 user interface.
■ The Vitocom 200 is connected to the Vitotronic control unit via LON.
The Vitocom 200 does not need to be configured for the LON.
On-site requirements:
Type LAN2
■ DSL router with free LAN socket and dynamic IP addressing
(DHCP).
■ Internet connection with flat rate data (without time or volume
restrictions).
■ LON communication module must be installed in the Vitotronic unit.
Note
For more information, see www.vitocom.info.
Standard delivery:
Type LAN2
■ Vitocom 200, type LAN2 with LAN socket.
■ LON communication module for installation in the Vitotronic control
unit.
■ Connecting cables for LAN and communication module.
■ Power cable with plug-in power supply unit (2.0 m long).
■ Vitodata 100 fault management for a duration of 3 years.
7
Note
For standard delivery of packs with Vitocom, see pricelist.
Accessories:
EM201 extension module
Part no.: Z012 116
■ 1 relay output for switching external appliances (contact breaking
capacity 230 V~, max. 2 A).
■ Max. one EM201 extension module per Vitocom 200.
VIESMANN
100
Specification:
2 6
3 4
Power supply via plug-in power sup-
ply unit
Rated frequency
Rated current
Power consumption
Safety category
IP rating
Permissible ambient temperature
– During operation
– During storage and transport
On-site connections:
– 2 digital inputs DI1 and DI2
– 1 digital output DO1
For further technical details and accessories, see the data communi-
cation technical guide.
. 5
230 V~/5 V–
50 Hz
250 mA
5 W
III
IP 30 to EN 60529, ensure
through design/installation
0 to +50 °C
Installation in living spaces or
boiler rooms (standard ambi-
ent conditions)
–20 to +85 °C
Floating contacts, contact load
24 V−, 7 mA
5 V–, 100 mA, for connecting
the EM201 extension module