Safety

The inverter is electronically protected. But protection against polarity inversions of the battery
occurs with an internal fuse, except for 2000W/12V inverter, which has no fuse. The following
table will show you the different failures and their consequences.
FAILURE
Low battery tension
Voltage < 1.8V/cel
Deep discharged battery
(voltage <1,5V/cel)
Overheat
Battery over voltage
Short circuit in the outlet
Overload
Inversion of the battery
polarity
CONSEQUENCE
Inverter momentarily
stopped, the green
indicator blinks.
Inverter stopped
Inverter momentarily
stopped, the green
indicator blinks.
Inverter stopped.
Inverter stopped.
Inverter stopped.
Internal fuse broken
down
7
SOLUTION
Automatic restart when the battery tension
rises
Inverter should be manually restarted
when the battery as reach 2V/cel
Automatic restart when the temperature
reaches the normal range.
Wait until the battery tension reaches the
correct level.
Push the ON/OFF switch to reactivate the
inverter.
Eliminate the short circuit.
Push the ON/OFF switch to reactivate the
inverter.
Use the inverter only in the range of its
nominal power. Regular use in overload
power diminished the lifetime of the
inverter.
Push the ON/OFF switch to reactivate the
inverter.
Back to manufacturer for testing

Hide quick links: