Sine wave inverter 19'' – HPSI serie
The series of industrial sine
wave inverters in 19'' rack is
directly developed from our SI
series. The HPSI range gains
therefore from a high reliability
and suits especially well to in-
dustrial and professional appli-
cations.
Technical specifications
HPSI
in 19" rack
Input voltage [Unom]
Nominal power
Standby current [mA]
Power ON no load standby power
Power ON no load
TWINPOWER system
Maximum efficiency
Weight [kg]
Height
depth [mm]
[HE] x
Input voltage
Output voltage
Distortion
Dynamic behaviour
Frequency
Charge detection
Maximum power load 15 min.
Maximum power load 3 min.
Peak power 5 sec.
Asymmetric charge
Cos φ max. at Pnom
IP protection index
Forced ventilation
Overheating protection
Required battery capacity
Acoustic level
EC conformity
Data are for information only and may change without notice
Other standard features:
. remote control possibility
. potential free alarm contact (60V/1A)
Options
HPSIxxxxTP
TWINPOWER system
HPSIxxxxPE
3-phase for 3 x 400V systems
HPSI 2212
12V
2200W
30
15W
--------
91%
35
< Unom x 0.95 - Unom x 1.33 >
Sinus 230 Vac +/- 3%
< 2% (at Pnom))
Normalization 0.5 ms for 0% to 100% load
50 Hz +/- 0.01%(Crystal control)
User adjustable: 0.5 to 20 W
1.3 – 1.6 x Pnom / 25°C
1.6 - 2 x Pnom / 25°C
3.5 x Pnom
Up to 2 x Pnom
0.6 - 1
IP 20
From 45°C +/- 3°C
75°C +/- 3°C
> 5 x Pnom/Unom (recommended value)
Without ventilation : < 20 dB With ventilation: < 45 dB
EN 50081 I/II, EN 55014 – 55022, IEC 801 II / III / IV, CEI 555, EN 60950
HPSI 4424
HPSI 4424
24V
4400W
35
<20W
--------
95%
51
264 (6U) x 450
Rear view of HPSI 4424
HPSI 5048
48V
5000W
30
<30W
--------
95%
57
545/HPSI