HPSI
in 19" rack
Input voltage [Unom]
Nominal power
Standby current [mA]
Power ON no load standby power
Power ON no load
TWINPOWER system
Maximum efficiency
Weight [kg]
Height
depth [mm]
[HE] x
Input voltage
Output voltage
Distortion
Dynamic behaviour
Frequency
Charge detection
Maximum power load 15 min.
Maximum power load 3 min.
Peak power 5 sec.
Asymmetric charge
Cos φ max. at Pnom
IP protection index
Forced ventilation
Overheating protection
Required battery capacity
Acoustic level
EC conformity
Data are for information only and may change without notice
Other standard features:
. remote control possibility
. potential free alarm contact (60V/1A)
Options
HPSIxxxxTP
TWINPOWER system
HPSIxxxxPE
3-phase for 3 x 400V systems
HPSI 2212
12V
2200W
30
15W
--------
91%
35
< Unom x 0.95 - Unom x 1.33 >
Sinus 230 Vac +/- 3%
< 2% (at Pnom))
Normalization 0.5 ms for 0% to 100% load
50 Hz +/- 0.01%(Crystal control)
User adjustable: 0.5 to 20 W
1.3 – 1.6 x Pnom / 25°C
1.6 - 2 x Pnom / 25°C
3.5 x Pnom
Up to 2 x Pnom
0.6 - 1
IP 20
From 45°C +/- 3°C
75°C +/- 3°C
> 5 x Pnom/Unom (recommended value)
Without ventilation : < 20 dB With ventilation: < 45 dB
EN 50081 I/II, EN 55014 – 55022, IEC 801 II / III / IV, CEI 555, EN 60950
HPSI 4424
HPSI 4424
24V
4400W
35
<20W
--------
95%
51
264 (6U) x 450
Rear view of HPSI 4424
HPSI 5048
48V
5000W
30
<30W
--------
95%
57
545/HPSI

Advertisement

Table of Contents
loading

Summary of Contents for Studer HPSI Series

  • Page 1 Sine wave inverter 19’’ – HPSI serie The series of industrial sine wave inverters in 19’’ rack is directly developed from our SI series. The HPSI range gains therefore from a high reliability and suits especially well to in- dustrial and professional appli- cations.
  • Page 2 STUDER INNOTEC Sinewave inverter HPSI series User's and Installer's Handbook STUDER INNOTEC Rue des Casernes 57 CH-1950 Sion Tel : ++41 (0)27 205 60 80 Fax: ++41 (0)27 205 60 88 info@studer-inno.com www.studer-inno.com Users’ and Installers’ Handbook HPSI V2.0 E...
  • Page 3: Table Of Contents

    STUDER INNOTEC Summary INTRODUCTION ..........................3 NOTE..............................3 APPLICATIONS AND PERFORMANCE ..................3 ASSEMBLY ............................3 ............................3 OCATION AIR-FLOW PATH ..........................4 CONNECTION............................. 4 USE ................................ 4 ..........................4 EMOTE CONTROL Standby Level (1) ........................... 4 Adjustment procedure ........................4 CONTROL ............................
  • Page 4: Introduction

    : battery. The installation of the "HPSI" can only be All inverters in the HPSI series are protected performed by a qualified technician. against overloading and short circuits. In case of malfunction, only a technician...
  • Page 5: Air-Flow Path

    STUDER INNOTEC The working device generates high tensions which could be fatal ! The inverter can be activated by moving the The place where the inverter is to be mounted switch to the “ Auto ” position. The “ on ”...
  • Page 6: Control

    Limitation of liability “ Autom. ” mode and no voltage is detected by the standby system. STUDER INNOTEC cannot control the installation, use and maintenance of the inverter. A 230 V tension is intermittently present! Thus, we are not responsible for damages,...
  • Page 7 We do not accept any responsibility for any violation of patent rights or other third person rights resulting from the use of the inverter. STUDER INNOTEC reserves the right to modify their products without previous notice Users’ and Installers’ Handbook HPSI V2.0 E...
  • Page 8: Declaration Of Conformity

    - IEC 801 II / III / IV - CEI 555 - LVD 73 / 23 / EEC - EMC Dir. 89 / 336 / EEC Full name / position Date Roland Studer / General director 16/02/2000 Signature Users’ and Installers’ Handbook HPSI V2.0 E page7...
  • Page 9: Equivalent Circuit For Hpsi Inverter

    STUDER inverters, or in any way resulting from an installation which is not in accordance with the in force regulations or for an inappropriate use of the inverter.
  • Page 10: Description And Wiring Diagram

    STUDER INNOTEC Description and wiring diagram Standby level adjustment (Not avalable with Twinpower option) Fault indicator (red LED) Run indicator (Green LED) Main switch Remote control connector( Inverter stop when contact is closed) Output 230 Vac (Caution! High voltage!) Plus battery...
  • Page 11: Technical Specifications

    STUDER INNOTEC TECHNICAL SPECIFICATIONS HPSI 2212 4424 5048 Model: (HPSI) (HPSI) (HPSI) in box 19’’ Input voltage [Unom] Nominal power 2200W 4400W 5000W Standby current Power ON no load standby power <20W <30W Maximum efficiency Height [HE] x depth [mm]...

This manual is also suitable for:

Hpsi 2212Hpsi 4424Hpsi 5048

Table of Contents