Function Setting - AirStage UTY-RSKY Installation Manual

Simple remote controller
Hide thumbs Also See for UTY-RSKY:
Table of Contents

Advertisement

Refrigerant circuit address setting
(6) When the "Address code" blinks set the Address code "02" by pressing
the " ▲" button or " ▼" button.
(7) "Address data" indicator blinks. Then set the Refrigerant circuit address
data by pressing the " ▲" button or " ▼" button.
(Range of setting is 00-99.)
(8) Fix the Refrigerant circuit address data by pressing
the "
" button. (Data is transferred to the indoor unit).
PROHIBITED
When Refrigerant circuit
address data is not set in the
indoor unit. (-- is displayed).
Set the Refrigerant circuit
address data again as per
procedure (6)-(8) above.
Completion of address setting mode
(9) Address setting mode is released and returns to normal indicator if the
" ▲" button, " ▼" button and "
5 seconds simultaneously.
* Address setting mode is released automatically if no key is pressed
for 60 seconds even the above buttons are not pressed.
(Switch to Address setting mode as per procedure (1) above.)
(10) After completing the ADDRESS SETTING, be sure to turn off the power
and turn it on again.
En-7
Address code
Refrigerant circuit address data
Ex. When Refrigerant circuit ad-
dress "18" is selected.
GOOD
When Refrigerant circuit
address data is set in the indoor
unit properly.
" button are pressed for more than
Normal mode indicator

9. FUNCTION SETTING

This procedure changes the function settings used to control the indoor unit
according to the installation conditions.
Incorrect settings can cause the indoor unit to malfunction.
Perform the "FUNCTION SETTING" according to the installation conditions
using the remote controller.
Refer to the indoor unit installation manual for details on the function
numbers and setting numbers.
Prepare for setting of indoor unit referring to installation manual of indoor
unit before start of functional setting.
Start of Function setting mode
(1) Press the " ▲" button, " ▼" button and "
5 seconds simultaneously. Then shift to Function setting mode.
(2) Press the " ▲" button or " ▼" button and select the Remote controller
address (Select the relevant indoor unit). Then press the "
Function number and setting number setting
(3) "Function number" indicator blinks. Then display Number by pressing
the " ▲" button or " ▼" button.
(4) When the "Setting number" blinks by pressing the "
Setting number by pressing the " ▲" button or " ▼" button.
" button for more than
Function setting mode initial indicator
" button.
Remote controller address
Ex. When Remote controller
address "01" is selected.
Function number
" button set the
Setting number
Ex. When Setting number "12"
is selected.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uty-rskgUty-rskyt

Table of Contents