andrews CSC 39 Installation Manual, Operation And Service Manual page 29

Table of Contents

Advertisement

SECTION 3
WATER
CONNECTIONS
Fig 12.
24
INSTALLATION
If higher flow rates are required for the cold water services, a suitable tee fitting should
be fitted to the pipework, upstream of item C1.
The pipework fitted to the tundish outlet should be one size larger than the outlet pipe of
the safety device and should be terminated at a suitable drain.
(See Building Regulations 1992 Approved Document G3).
All fittings and materials must be suitable for use with drinking water and listed in the
current Water Research Centre " Materials and Fittings Directory".
Installation of unvented hot storage water systems must comply with Part G3 of the
Building Regulations 1992.
Typical water service layout for unvented system is shown in Fig 12.
Hot Water Service
Optional Hot Water
Service
Secondary Return
Check Valve
To Drain
Balanced
Cold Water
Take Off
Cold Water
Inlet Valve

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cscl 59Cscl 93Cscl 78Cscl 39Csc59Csc93

Table of Contents