3. Neutral to Ground Filter Jumper
All LowProfile models with enhanced filter (model numbers end with "-F" suffix) come with a green jumper wire, which
loops out of the epoxy and connects the filter from neutral to ground. In certain medical applications or circuits which
employ GFCI protection, this Neutral to Ground filter connection should be removed.
WARNING: Prior to proceeding, ensure the LowProfile unit does not have voltage applied to its input
!
terminals
Removal is accomplished by cutting the green jumper wire. Once cut, both ends should be properly separated and insulated
to prevent the ends from making inadvertent electrical contact.
™