Fig. 47—Burner Orifice
DO NOT redrill orifices. Improper drilling (burrs, out-of-
round hole, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame
impingement of burners and heat exchangers causing failures.
(See Fig. 47.)
BURNER FLAME
MANIFOLD
Fig. 48—Burner Flame
NOTE: Be sure all pressure tubing, combustion-air and vent
pipes, and burner enclosure front are in place when checking input
by clocking gas meter.
a. Calculate high-altitude adjustment (if required).
Table 10—Altitude Derate Multiplier for U.S.A.
ALTITUDE
% OF
(FT)
DERATE
0—2000
0
2001—3000
4—6
3001—4000
6—8
4001—5000
8—10
5001—6000
10—12
6001—7000
12—14
7001—8000
14—16
8001—9000
16—18
9001—10,000
18—20
* Derate multiplier factor is based on midpoint altitude for altitude range.
United States
At altitudes above 2000 ft, this furnace has been approved for a 2%
derate for each 1000 ft above sea level. See Table 10 for derate
BURNER
ORIFICE
A93059
BURNER
A89020
DERATE MULTIPLIER
FACTOR FOR U.S.A*
1.00
0.95
0.93
0.91
0.89
0.87
0.85
0.83
0.81
41
multiplier factor.
EXAMPLE: 100,000 Btuh input furnace installed at 4300 ft.
Derate
Furnace Input Rate
X
Multiplier
at Sea Level
100,000
X
Canada
At installation altitudes from 2001 to 4500 ft, this furnace must be
derated 5% by an authorized Gas Conversion Station. To deter-
mine correct input rate for altitude, see example above and use
0.95 as derate multiplier factor.
b. Reinstall burner box cover.
c. Gas valve regulator seal cap MUST be installed.
d. Turn off all other gas appliances and pilots.
e. Start furnace and let operate for 3 minutes.
f. Measure time (in sec) for gas meter test dial to complete 1
revolution.
g. Refer to Table 11 for cu ft of gas per hr.
Table 11—Gas Rate (Cu Ft/Hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367
h. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)
using natural gas heating value from local gas
utility/supplier.
Furnace Input Rate
=
at Installation
Factor
Altitude
0.91
=
91,000
SIZE OF TEST DIAL
SECONDS
FOR 1
5
1
2
REVOLUTION
cu ft
cu ft
50
72
144
51
71
141
52
69
138
53
68
136
54
67
133
55
65
131
56
64
129
57
63
126
58
62
124
59
61
122
60
60
120
62
58
116
64
56
112
66
54
109
68
53
106
70
51
103
72
50
100
74
48
97
76
47
95
78
46
92
80
45
90
82
44
88
84
43
86
86
42
84
88
41
82
90
40
80
92
39
78
94
38
76
96
38
75
98
37
74
100
36
72
102
35
71
104
35
69
106
34
68
108
33
67
110
33
65
112
32
64
116
31
62
120
30
60
124
29
58
5
cu ft
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150
145

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents