LG ThermaV Owner's Manual page 28

Air-to-water heat pump
Hide thumbs Also See for ThermaV:
Table of Contents

Advertisement

Installation instruction
Installer Setting-Setting Outdoor Temperature range for Weather-dependent operation
Determining Outdoor air Temp. concerned with autosetting of setting temperature according to
Outdoor air Temp. Two points, x1 and x2 in the Temperature Profile, are chosen.
Note
• All values are in °C.
• Selection of °C or °F is based on
the value of Function Code 04.
Temperature Profile
Setting Temp
(Air or Water)
x1
Value #1
28 Air-to-Water Heat Pump Owner's Manual
x2
Outdoor
air Temp.
Value #2
1
Keep pressing Function Setting
button for 3 seconds to enter
installer setting mode until
code displayed in timer segment.
2
Repeat pressing button to select
Function code 23.
Value
Note
Value #1
Lower Limit of setting range
Value #2
Upper Limit of setting range
3
Set the Value #1 by pressing up, down button.
Ex) setting Value as Value #1 = '-15'
Value #2 = '10'
4
Move to Value #2 part by pressing right
direction button.
5
Set the Value #2 by pressing up, down
button.
6
If you finish the setting, press set / clear
button to save the setting.
7
Press
button to exit or system will
automatically exit after 25 seconds
without any input.
Value #1
Value #2
Default
Range
-10
-20~05
15
10~20

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents