Installer Setting -Setting Leaving Water Temperature in Heating Mode
Determine heating setting temperature range when leaving water temperature is selected as setting temperature.
Following instruction shows how to change the range of setting temperature from 15°C~55°C to 30°C~45 °C.
Note
• All values are in °C.
• Selection of °C or °F is based on the
value of Function Code 04.
1
Keep pressing Function Setting
button for 3 seconds to enter
installer setting mode until
code displayed in timer segment.
2
Repeat pressing button to select
Function code 14.
Value
Note
Value #1
Upper Limit of setting range
Value #2
Lower Limit of setting range
3
Set the Value #1 by pressing up, down button.
Ex) setting Value as Value #1 = '45'
Value #2 = '30'
4
Move to Value #2 part by pressing right
direction button.
5
Set the Value #2 by pressing up, down
button.
6
If you finish the setting, press set / clear
button to save the setting.
7
Press
button to exit or system will
automatically exit after 25 seconds
without any input.
Installation instruction
Value #1 : Upper
Limit of setting range
Value #2 : Lower
Limit of setting range
Default
Range
55
40~55
15
15~37