Specifications - HydroTherm HeatNet KN -6 User Information

Kn series gas-fired direct vent cast iron boilers
Table of Contents

Advertisement

FEATURES & SPECIFICATIONS

Specifications

Control
Environment
Input Power
Relays
AC Interlocks
Control Inputs
Dimensions
Temperature Sensors
USB
RS485 MODBUS
Boiler-to-Boiler
Network
Microprocessor based PID modulating control ( NOT a safety limit )
-40 °F to 140 °F, <90% RH non-condensing
24 VAC, 500 ma
System Pump, Damper, Circulator, Alarm, DHW Pump (v2.x), 8A 250 VAC resistive
K8 on J4.2 &.6 for Base Loading version 2.x Control
24 VAC – 120 VAC input
AA, Heat Demand, 4-20ma Enable, OA override, T1-T2 (dry contact inputs)
4-20mA, 0-10 VDC
9‖ wide: 6‖ high : 2‖ deep
NTC thermistor, 10K @ 77 °F, 335.67K @ -40 °F, 185 @ 150 °F ,+/- 1 F
1.0
Modbus RTU
HeatNet (H-Net)
Optional LonWorks, BACnet available bridge to MODBUS port
HeatNet Control V3 2.x
Page 8

Hide quick links:

Advertisement

Table of Contents
loading