DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
MORE MENUS
ZERO RUNTIME
PUMP1 TIME
PUMP2 TIME
ALWAYS ENABLED
SUMMER PUMP JOG
OVR ENAB IN WWS
LOCAL PUMP
DELTA TEMP ENAB
DELTA TEMP
POST PRGE TIME
ALWAYS ENABLED
PUMP/VALVE OPTIONS
MASTER PUMP/VALVE
REMAINS ON:
LOCAL PUMP VFD
FLOW PROVE
SETBACK ENTRY
ENTRY IS
SETBACK
START DAY
TIME
END DAY
PUMP1
PUMP1- PUMP2
0-999999 hrs
0-999999 hrs
OFF
ON/OFF
ON/OFF
OFF
MON-SUN
OFF
ON/OFF
OFF
(2 – 50 F)
10 °F
2 minutes
(1-60min)
OFF
OFF
ON/OFF
OFF
ON/OFF
10s
10-240 sec
NIGHT SETBACK
(1 – 4)
1
OFF
20 F
(0 – 50 F)
MON
12:00AM
MON
If ROTATION is set to PUMP HRS, ROTATE TIME is used to
switch pumps when the pump's time difference is greater than
ROTATE TIME. Whichever pump has the least time and is at least
below the other (pump's time - ROTATE TIME) will switch to the
enabled state. This selection is used to equalize run time on the
pumps.
New menu screen follows.
This menu allows the clearing of a pump's runtime counter.
Discretion is advised in clearing only one pump's hours after
replacement and then using ROTATION set to PUMP HRS. This
would cause the pump whose runtime was cleared to run until it's
time exceeded the other older pump.
Indicates how many hours the HeatNet control has accumulated on
pump 1.
Indicates how many hours the HeatNet control has accumulated on
pump 2.
ON = Pump never shuts off. Used when there is only 1 system pump
in the system.
Used with Outdoor Reset, Jogs the local and system pump(s) for
POST PRGE time when system is in summer shutdown. Jog once a
week @12:00 AM.
The menu item OVR ENAB IN WWS and ALWAYS ENABLED
must be set to OFF for the jog function to work,
Priority mode for the system pump while in Warm Weather
Shutdown. ON: The system pump is allowed to run in WWS when
the OR OVR override input is closed. When set to OFF, the system
pump will not come on while in WWS with the OR OVR override
input closed. Enabling this feature disables the SUMMER PUMP
JOG.
ON: Use Delta temperature to shut pump off when temperature
across boiler is less than DELTA TEMP setting.
Time in minutes to keep local circ. pump on after boiler stops
Pump never shuts off.
ON: The master boiler will keep its pump/valve on when no boilers
are running. Prevents deadheading the system flow.
ON: Outputs a 0-10VDC or 4-20mA signal from J4 pins 1 & 5 that is
proportional to the fire rate of the boiler. Connect to a VFD
controlling a Local pump.
This is an adjustable flow proving time to allow slower valves to
open before proving flow.
Four setbacks to adjust setpoint during a time period
Enable or disable the use of this setback
Temporarily subtracts this temp from the setpoint
Day of the week to begin setback or a day range
Time to begin setback
Day of the week to end the setback or a day range
HeatNet Control V3 2.x
Page 62