Setpoint Priorities - HydroTherm HeatNet KN -6 User Information

Kn series gas-fired direct vent cast iron boilers
Table of Contents

Advertisement

OPTIONAL FEATURES
For non Ametek blowers, the minimum setting
of the boiler is calibrated so that the minimum
PWM signal to control the Blower motor is
20%. The VFD to blower motor operates with a
control signal from 20% - 80% Pulse Width
Modulation. This PWM signal to the VFD can
be measured using a multimeter. It is a 0–
10volt square wave signal at 110 Hertz. A 20%
modulation signal will read 2.0 VDC, and an
80% modulation signal will read 8.0 VDC on
an RMS multimeter. See Figure 36, page 56.
For Ametek Blowers, the minimum signal to
control the blower will be less than 20%, but
the display % will be equal to the turndown %
of the boiler. Also, the signal sent to the
Ametek blower is twice that of non Ametek
blowers, so the VDC reading will need to be
divided by (2) to get the modulation % sent to
the Blower. The Ametek blower also has a
menu located at: ADVANCED
SETUP:BLOWER SETTINGS. This menu
allows the Acceleration, Deceleration, and Soft
Start Values to be set for proper operation of
the Blower.
For direct fire applications, the 0-10 volt
control signal is proportional to the output.
Such that: 1 volt will track linearly by 10%. So,
1v=10%, 2v=20%, 3v=30%, 4v=40%... The
control signal will still be limited by the
turndown and the 4-20mA INPUT menu. This
means that the 1v signal will have no effect on
a 5:1, 20% boiler. A ~2v signal will start the
5:1 boiler.
Setpoint Control functionality can be implemented remotely
using the 4-20mA input. This function translates a 4 to 20ma
control signal to a setpoint mapped from 50F to 220F. The
feature is enabled in the SETPOINTS menu as: SETUP:
SETPOINTS:SETPT SOURCE 4-20ma.
ADVANCED SETUP:4-20ma INPUT:CHANNEL MODE.
Also, when selecting; SETUP:SETPOINTS:SETPT SOURCE
and selecting 4-20ma, the 4-20ma INPUT menu will be
automatically entered.
You may now select the current at which the boiler will start.
It is adjustable from 3.7ma to 5ma. Hysteresis of .1ma is
always in effect. So, if the starting ma = 4.10ma the boiler
will start when the control current applied achieves this value
of 4.10ma. The boiler must drop .1ma below this to turn OFF,
in this example 4.00ma. This hysteresis value is not
adjustable.
When using the 4-20ma setpoint control, a band may now be
set at which the 4-20ma signal will operate over. The lower
setpoint is defined as 4ma SETPOINT and the upper setpoint
is defined as 20ma SETPOINT. The 4ma SETPOINT is
linked to the BOILER START x.xxma where this starting
current is the lower setpoint. So, if we set the 4ma
SETPOINT to 130F and the 20ma SETPOINT at 180F we
will have established the band. Once a starting control current
of BOILER START 4.1mA is applied, and the 4-20
REMOTE ENABLE INPUT is closed, the boiler will start and
the setpoint will be set to 130F. If a control current of 10ma is
applied the boiler will track on a linear slope towards the
20ma SETPOINT settling at a SETPOINT of ~149F. As the
current increases to 20ma, the SETPOINT will indicate 180F.
The Default setting is 4ma SETPOINT: 50F, and 20ma
SETPOINT 220F for backwards compatibility with the older
version. NOTE: anytime a new firmware version is uploaded
to the control, these values return these defaults.
Anytime a new firmware version is uploaded to
the control, these values return to these
defaults.
If using the direct modulation mode by applying a 4-20ma
current, only the BOILER START x.xx setting applies.
The 4-20 mA input can be set to HIGH PRIORITY. This is
done in menu: ADVANCED SETUP:4-20mA
INPUT:CHANNEL MODE. This allows a member boiler to
be taken offline and directly modulated by an external control.
If the Master is using it for heating and the 4-20mA is set to
HIGH PRIORITY, an external control can now output a 4-
20mA signal which will take over the boiler's fire rate. This is
typically used for DHW control.

Setpoint Priorities

Changing the setpoint can be done in many ways. If a higher
level setpoint control is lost, the next level setpoint control is
used until the System Setpoint is loaded. The setpoints are
prioritized in the following order:
1.
0-10V, 4-20Ma setpoint Control
2.
BMS, Modbus Setpoint
3.
Outdoor Reset Setpoint
Menu's System Setpoint
4.
Any Setbacks that are active are then applied.
HeatNet Control V3 2.x
Page 29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents