HydroTherm HeatNet KN -6 User Information page 5

Kn series gas-fired direct vent cast iron boilers
Table of Contents

Advertisement

FEATURES & SPECIFICATIONS
100%. This ―boiler efficiency‖ clamp is defaulted to 70%
and thus limits all of the boilers individual outputs to 70%
until the last boiler fires. All running boilers modulate up
and down together, always at the same modulation rate. As
a general rule, this percentage should be no lower than twice
the minimum turndown to minimize short cycling.
When additional boilers are needed to achieve setpoint in
the system, the Master boiler employs an ADAPTIVE
MODULATION algorithm to prevent over firing of the
system. The Master communicates over the H-Net to view
the exact status of each Member boiler. When a new boiler
is added, the Master boiler adjusts the system modulation
rate lower to compensate for the BTUs that will be
introduced by the newly added boiler. This adjustment
occurs when the newly added Member boiler enters its ON
CALL state (default setting). This can be changed to PILOT
when the new boiler is called using the menu:
ADVANCED SETUP:ADAPTIVE MOD:DROP
DOWN. Once the Main Valve (on the newly added boiler)
is opened, and the DELAY RELEASE timer equals zero,
the PID algorithm is allowed to control the system
modulation. Setting the DELAY RELEASE timer will
allow some ―soak‖ time of the newly added boiler before
releasing modulation control to the PID.
The ADAPTIVE MOD menus are disabled
on a Member boiler, but are still visible.
Member
If a ―SYS/DHW HEADER‖ sensor is not connected to J10,
a boiler always defaults to the role of Member.
The Member boiler can operate as part of a multi-boiler
system or as a stand-alone unit.
In a multi-boiler system the Member typically receives its
command signals from a designated Master-boiler. It is also
capable of receiving inputs from an external control system.
The boiler responds to these signals, to start/stop the burner,
and/or to modulate the firing rate. The outlet water
temperature is also monitored. If the outlet temperature
approaches the operating limit temperature setpoint
(adjustable), the boilers firing rate is limited and its
modulation value is reduced to minimize short-cycling. If
the operating limit is exceeded, or if an interlock trips, the
boiler is shut down. When connected with a network cable,
in a Master/Member role, the Members' status is
interrogated by the Master boiler.
In a stand-alone installation the Member typically receives
its command signals internally and operates based upon the
outlet water temperature input and the established settings in
the menu (Local Set-point) to start/stop the burner, and/or to
modulate the firing rate. If the operating limit is exceeded,
or if an interlock trips, the boiler is shut down. As in a
multi-boiler system, a stand-alone Member boiler is also
capable of receiving inputs from an external control system.
When using the H-Net network cable in a Master/Member
system, the system setpoint is sent from the Master as a
digital signal, along with the modulation value to control
firing rate. It also receives its command to start or stop over
the H-Net cable. Also, the SYSTEM CLOCK only needs to
be set on the MASTER. The Master will then set the time
on all member boilers.
If not using the H-Net protocol (cable), an external control
can send a 4-20ma signal along with a 4-20ma enable signal
to control the firing rate or setpoint. The boiler may also be
treated as a 2-stage boiler or an ON-OFF boiler using the
dedicated T-inputs.
HeatNet Control V3 2.x
Page 5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents