HydroTherm HeatNet KN -6 User Information page 63

Kn series gas-fired direct vent cast iron boilers
Table of Contents

Advertisement

DEFAULT SETTINGS & MENU ITEM DESCRIPTIONS
TIME
TEMP SCALE
KEY CLICK
SKIP PASSWORD
BRIGHTNESS
RUN HOURS
DATA LOG ENTRY
SIZE
BOILER CYCLES
COMBUST AIR
DAMPER
TYPE
IN USE?
INPUT:
PROOF TIME
ALARM SILENCE
ALARM SILENCE IN
USE?
INPUT =
FAILSAFE MODES
RUN IN LOCAL IF:
H-NET COMM LOST
12:00AM
F
(F or C)
ON
ON
50%
(25, 50,75,100)
LINKED/COMMON
INDEPENDENT
YES
J12B.7
DAMPER
(0 – 4min)
2:00
YES
J10B STACK
OFF
Time of the day to end the setback
OPTIONS
Fahrenheit scale is default
Beeps when a key is pressed
Disables the Password
Four levels of display brightness, lower for longer life of the display
LOG/RUNTIME
Displays runtime hours. Total time the main valve has been open.
Displays the current entry in the data log
Displays the current size of the log in entries
Displays completed boiler cycles. Incremented when the main valve
turns OFF after it has been ON. Does not include attempts to light.
AUX FUNCTIONS
The LINKED/COMMON setting allows one common damper to be
used and controlled by the Master Boiler. All Member boilers must
have their damper prove inputs wired as per Figure 37, Common
system damper wiring, page 57. Also see Section: Optional
Features: Auxiliary Function Options INDEPENDENT: Individual
dampers are in controlled by their respective boiler.
If set to YES, then OUTPUT RELAY K5 can be used to control a
combustion air damper. The Master can control a common system
damper or an individual damper. Members control their respective
damper independent of the Master. Relay K5 is used to enable the
combustion air damper. See Figure 37, Common system damper
wiring, page 57. Needs to Prove the damper is open.
The damper prove input is dedicated to connect at J12B terminals 7
and 8. If using a common damper refer to the common damper
wiring diagram.
This is the proving time in minutes for the combustion air damper
prove switch. It is sensed at J12B Pin 7. If the damper faults, a retry
will occur every 10 minutes in attempt to open the damper.
When using J12B in a common damper configuration, wiring is done
beginning with the Master boiler. J12B Pins 7,8 are connected to the
prove switch of the combustion damper. Pin 8 is supplying 24 VAC
and pin 7 is the sense input. A second wire is connected to J12B pin
7 of the Master and the other end connected to the first member
boilers J12B pin 7. If another member boiler is present, connect
another wire to the J12B Pin 7 terminal of the first member and the
other end to the second member boiler J12B pin 7. Continue this
method for each additional boiler.
This menu allows the configuration of the Alarm Silence switch. It
can be disabled so that the Alarm Silence switch cannot silence the
alarm until the alarm is cleared; ALARM SILENCE = NO. The
default value is to enable the ALARM SILENCE switch. Holding
down the BACK and SELECT keys at the same time may also be
used to silence the alarm.
If a stack sensor is used, holding down the BACK and SELECT keys
at the same time is the only way to silence the alarm.
If this entry is set to ON and the Member boiler does not see any
communications coming from the Master boiler, this boiler will run
HeatNet Control V3 2.x
Page 63