5.2 Remote Register Assignment

5.2.1 Remote registers (master unit → → → → inverter (FR-E5NC))
Device No.
Signal
RW
Monitor code
W0
RW
Set frequency
W1
RW
Instruction code
W2
RW
Write data
W3
5.2.2 Remote registers (inverter (FR-E5NC) → → → → master unit)
RWr
Monitored value
0
RWr
Output frequency
1
RWr
Reply code
2
RWr
Read data
3
Set the monitor code to be referenced. By switching on the RYC signal after setting, the
specified monitored data is set to RWr
Specify the set frequency. At this time, whether it is written to RAM or E
differentiated by the RYD and RYE signals. After setting the frequency to this register, switch
on the above RYD or RYE to write the frequency. On completion of frequency write, RXD or
RXE switches on in response to the input command.
Set the instruction code for execution of operation mode rewrite, Pr. read/write, error
reference, error clear, etc. (refer to page 29). The corresponding instruction is executed by
switching on RYF after completion of register setting. RXF switches on on completion of
instruction execution.
Set the data specified by the above instruction code. (When required)
Switch RYF on after setting the above instruction code and this register.
Set zero when the write code is not required.
The monitored value specified by RW
The present output frequency is always set.
The reply code corresponding to RW
and a value other than 0 is set for a data error.
For a normal reply, the reply data to the instruction specified by the instruction code is set.
28
COMMUNICATION SPECIFICATIONS
Description
.
0
(monitor code) is set.
W0
(instruction code) is set. 0 is set for a normal reply
W2
2
PROM is