Troubleshooting Guide
The house heating comfort is not adjusted to the customer's requirements
Action:
Check the ROOM, CURVE and MIN settings. Adjust incorrect values in the heat pump's control computer.
ROOM = Desired indoor temperature
CURVE = Should be set so that the desired indoor temperature is maintained regardless of the outdoor temperature.
MIN = Lowest set-point value on the supply line regardless of the outdoor temperature, except with heat stop.
Sensor fault, Outdoor, room, supply line
Action:
Check what the relevant sensor shows. Is it a plausible/actual value?
Measure the resistance of the sensor, check against the ohm table in the installation instructions. If it is not correct calibrate or replace
the sensor.