21 21

Accessories

For installation purposes, be sure to use the parts supplied by the manufacturer or
other prescribed parts.
The use of non-prescribed parts can cause serious accidents such as the unit falling,
water leakage, electric shock, or fire.
The following installation parts are furnished. Use them as required.
Keep the Installation Manual in a safe place and do not discard any other accessories
until the installation work has been completed.
Name and Shape
Special nut A
(Large flange)
Special nut A
(small flange)
Coupler heat insulation (Large)
Coupler heat insulation (Small)
Cable tie (Large)
Cable tie (Medium)
Cable tie (Small)
Remote controller
Screw
(Flush heads)
Remote controller cable
21 41

Optional parts

Parts name
Wired remote controller
Wired remote controller
Simple remote controller
Remote sensor
External control set
WARNING
Q'ty
Description
4
For suspending the indoor unit
from ceiling
4
For indoor side pipe joint
1
(Gas pipe)
For indoor side pipe joint
1
(Liquid pipe)
4
For fixing the heat insulation
For fixing the remote controller
4
cable and connection cable
For fixing the remote controller
1
cable
1
For Air conditioner operation
For installing indoor unit remote
2
controller
For connecting the remote
1
controller
Model No.
Summary
For Air conditioner
UTY-RVN*M
operation
For Air conditioner
UTY-RNN*M
operation
For Air conditioner
UTY-RSN*M
operation
New amenity space can
be offered by installing
UTY-XSZX
the Remote sensor in the
remote controller
Use to connect various
UTD-ECS5A
peripheral devices and air
conditioner PC board
21

INSTALLATION WORK

Especially, the installation place is very important for the split type air conditioner because
it is very difficult to move from place to place after the first installation.
21 11

Selecting an installation location

Decide the mounting position together with the customer as follows.
Select installation locations that can properly support the weight of the indoor unit.
Install the units securely so that they do not topple or fall.
Do not install the indoor unit in the following areas:
Area with high salt content, such as at the seaside.
It will deteriorate metal parts, causing the parts to fall or the unit to leak water.
Area filled with mineral oil or containing a large amount of splashed oil or steam,
such as a kitchen.
It will deteriorate plastic parts, causing the parts to fall or the unit to leak water.
Area that generates substances that adversely affect the equipment, such as sulfuric
gas, chlorine gas, acid, or alkali. It will cause the copper pipes and brazed joints to
corrode, which can cause refrigerant leakage.
Area that can cause combustible gas to leak, contains suspended carbon fibers or
flammable dust, or volatile inflammables such as paint thinner or gasoline. If gas
leaks and settles around the unit, it can cause a fire.
Area where animals may urinate on the unit or ammonia may be generated.
Do not use the unit for special purposes, such as storing food, raising animals, growing
plants, or preserving precision devices or art objects. It can degrade the quality of the
preserved or stored objects.
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
Install the unit where drainage does not cause any trouble.
Install the indoor unit, outdoor unit, power supply cable, transmission cable, and remote
control cable at least 1 m away from a television or radio receivers. The purpose of this
is to prevent TV reception interference or radio noise.
(Even if they are installed more than 1 m apart, you could still receive noise under
some signal conditions.)
Install the unit where ambient temperature does not reach 60°C or more.
Take a measure such as ventilation for an environment in which heat is retained.
If children under 10 years old may approach the unit, take preventive measures so that
they cannot reach the unit.
Take precautions to prevent the unit from falling.
(1)
Install the indoor unit on a place having a sufficient strength so that it withstands
against the weight of the indoor unit.
(2)
The inlet and outlet ports should not be obstructed; the air should be able to blow all
over the room.
(3)
Leave the space required to service the air conditioner.
(4)
Install the unit where connection to the outdoor unit is easy.
(5)
Install the unit where the connection pipe can be easily installed.
(6)
Install the unit where the drain pipe can be easily installed.
(7)
Install the unit where noise and vibrations are not amplified.
(8)
Take servicing, etc., into consideration and leave the spaces. Also install the unit where
the filter can be removed.
(9)
Do not install the unit where it will be exposed to direct sunlight.
21 21

Installation dimension

21 21 11
Installation by which service space is made on top of the unit
(recommended)
Install the unit away from the ceiling by 350 mm or more.
350
or
more
Unit : mm
2500 or more
(When no ceiling)
Floor
WARNING
CAUTION
Service
space
500 or more
Service access
En-2