Bosch Integra 500 Installation Manual page 11

Temperature modulated with electronic ignition
Hide thumbs Also See for Integra 500:
Table of Contents

Advertisement

3.3.2
Vent specifications
Establish vent clearances that comply with the vent
manufacturer's
specifications
national/local codes.
Venting specifications
Diam.
E
x
h
a
3 or 4 inches
u
s
t
I
n
t
3 or 4 inches
a
k
e
Table 4 Venting specifications for intake and exhaust
Condensate drain requirements
An external condensate drain (not supplied with the
heater) must be installed under the following
conditions:
• All vertical terminating vent installations.
• Horizontal terminating vent installations where the
total linear vent length is greater than 6 feet (1.8 m).
• Vent installations where any section of the exhaust
vent pipe passes through an unconditioned space.
Minimum combustion air and exhaust pipe
length
The minimum exhaust pipe length is 3 feet (1m) of
straight vent pipe. The minimum combustion air pipe
length is one 90° elbow.
Maximum combustion air and exhaust pipe
length
The following tables (Tables 5 & 6) display the
maximum
allowable
straight
combustion air and exhaust piping with consideration to
the number of elbows used.
Note:
90°
i
terminations should not be counted
in the exhaust and combustion air
piping.
6 720 680 226
and
all
applicable
Aproved terminals
"T" terminal
90° elbow
Concentric
(196016)
"T" terminal
90° elbow
Concentric
(196016)
pipe
lengths
elbows
used
for
Step 1: If using the twin pipe penetration system, refer
to table 5. If using the concentric vent kit
system, refer to table 6.
Step 2: Total the number of 90° elbows and 45°
elbows used on the exhaust piping.
Step 3: Use this value in the appropriate table to
determine the maximum straight exhaust pipe
length allowed.
Step 4: Total the number of 90° elbows and 45°
elbows used on the combustion air piping.
Step 5: Use this value in the appropriate table to
determine the maximum straight combustion
air pipe length allowed.
Twin Pipe
System
0
N/A*
N/A*
1
2
# of 45°
3
elbows
4
5
6
Maximum allowable straight pipe length (ft)
Table 5 Maximum allowable straight pipe length (twin
pipe)
*
Not allowed. At least one 90º elbow required.
**
Not allowed. Minimum of 3 feet (1m) of straight pipe required.
Concentric
pipe System
0
N/A*
N/A*
1
for
2
# of 45°
3
elbows
4
5
6
Maximum allowable straight pipe length (ft)
Table 6 Maximum straight pipe length (concentric ter-
minal)
*
Not allowed. At least one 90º elbow required.
**
Not allowed. Minimum of 3 feet (1m) of straight pipe required.
Note: Include pipe length that is part of the concentric terminal.
Installation instructions
# of 90° elbows
0
1
2
26
21
16
23
18
13
23
20
15
10
20
17
12
17
14
9
14
11
6
N/A**
11
8
3
N/A**
# of 90° elbows
0
1
2
18
13
15
10
15
12
7
N/A**
12
9
4
N/A**
9
6
N/A**
N/A**
6
3
N/A**
N/A**
3
N/A**
N/A**
N/A**
3
4
11
8
5
7
N/A**
4
N/A**
N/A**
N/A**
3
4
8
3
5
N/A**
N/A**
N/A**
N/A**
N/A**
N/A**
11