Bosch Integra 500 Installation Manual page 12

Temperature modulated with electronic ignition
Hide thumbs Also See for Integra 500:
Table of Contents

Advertisement

Installation instructions
Required direct vent terminal clearances (twin pipe / concentric penetration)
Fig. 9
A
Clearance above grade, veranda, porch, deck or balcony
B
Clearance to window or door that may be opened
Clearance to permanently closed window
C
Vertical clearance to ventilated soffit located above the vent
D
terminator within a horizontal distance of 2 feet (61cm) from the
center line of the terminator
E
Clearance to unventilated soffit
F
Clearance to outside corner
G
Clearance to inside corner
H
Clearance to each side of center line extended above meter/
regulator assembly
I
Clearance to service regulator vent outlet
J
Clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other application
K
Clearance to mechanical air supply inlet
L
Clearance above paved sidewalk or paved driveway located on
public property
M
Clearance under veranda, porch deck or balcony
Table 7
1)
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2)
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
3)
A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
4)
Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
*
For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA-B149.1, one of the following shall be indicated:
a) A minimum clearance value determined by testing in accordance with section 2.20, or;
b) A reference to the following footnote:
"Clearance in accordance with local installation codes and the requirements of the gas supplier."
12
1)
Canadian installations
12 in.
36 in.
*
*
*
*
*
36 in. within a height 15 feet above
meter/ regulator assembly
36 in.
36 in.
72 in.
3)
84 in.
4)
12 in.
6720608836-23.1Av
2)
U.S. installations
12 in.
12 in.
*
*
*
*
*
*
*
12 in.
36 in. above if within 10 feet
horizontally
*
*
6 720 680 226