Unitary products group GY8S*DH Installation Manual

High efficiency tubular heat exchanger series
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL

HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: GY8S*DH / GM8S*DH / LY8S*DH / LM8S*DH
(Single Stage Downflow / Horizontal / Low NOx)
40 - 130 MBH INPUT
(11.72 - 38.10 KW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Downflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Typical Twinned Furnace Application . . . . . . . . . . . . . . . . . . . . . . . . 12
Single Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . 13
Two-Stage Twinning Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vent Termination 10 ft. (3.0 m) or less . . . . . . . . . . . . . . . . . . . . . . . . 14
Vent Termination more than 10 ft. (3.0 m) . . . . . . . . . . . . . . . . . . . . . 14
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Recommended Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
TWINNING AND STAGING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .20
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
LIST OF FIGURES
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Typical Sidewall Vent Application . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .17
Typical Chimney Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .18
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
LIST OF TABLES
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .18
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Blower Performance CFM - (without filter) . . . . . . . . . . . . . . . . . . . . .25
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .26
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
268894-UIM-A-0407

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GY8S*DH and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group GY8S*DH

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING CERTIFIED TUBULAR HEAT EXCHANGER SERIES MODELS: GY8S*DH / GM8S*DH / LY8S*DH / LM8S*DH (Single Stage Downflow / Horizontal / Low NOx) ISO 9001 Certified Quality Management System 40 - 130 MBH INPUT (11.72 - 38.10 KW) INPUT LIST OF SECTIONS SAFETY .
  • Page 2: Safety

    When outdoor air is used for combustion, the combustion air intake duct of standard ANSI Z21-47 • CSA 2.3. system termination must be located external to the building and in an area where there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3 INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes car- bon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. Unitary Products Group...
  • Page 4: Ductwork

    The ducts attached to the furnace plenum, should be of sufficient size so that the furnace operates at the specified external static pressure and within the air temperature rise specified on the nameplate. Unitary Products Group...
  • Page 5: Combustible Floor Base Accessory

    There are several variables associated with proper duct sizing that are not included in the tables. To properly design the ductwork for the build- ing, refer to the ASHRAE Fundamentals Handbook, chapter on “DUCT DESIGN” or a company that specializes in Residential and Modular Unitary Products Group...
  • Page 6: Typical Attic Installation

    Unitary Products Group...
  • Page 7: Typical Suspended Furnace / Crawl Space Installation

    1600 (45.3) 53.3 19 3/4 50.2 18-1/2 47.0 13 1/2 34.3 115 (33.7) 2000 (56.6) 53.3 19 3/4 50.2 18-1/2 47.0 13 1/2 34.3 130 (38.1) 2000 (56.6) 24 1/2 62.2 23 1/4 59.1 55.9 15 1/4 38.7 Unitary Products Group...
  • Page 8: Filters

    IMPORTANT: Plan your gas supply before determining the correct gas pipe entry. Use 90-degree service elbow(s), or short nipples and con- MANUAL ventional 90-degree elbow(s) to enter through the cabinet access holes. DRIP SHUT-OFF VALVE FIGURE 7: Horizontal Gas Piping Unitary Products Group...
  • Page 9: Electrical Power

    Field wiring to the unit must be grounded. Electric wires that are field Use copper conductors only. installed shall conform to the temperature limitation of 63°F (35°C) rise when installed in accordance with these instructions. Refer to Table 7 in these instructions for specific furnace electrical data. Unitary Products Group...
  • Page 10: Electrical Wiring

    Refer to on the condensing unit (unit outside). "FURNACE DIAGNOSTICS" section of the “User’s Information, Maintenance, & Service Manual” provided with this furnace for symptoms of reversed power supply polarity. Unitary Products Group...
  • Page 11: Thermostat Chart

    268894-UIM-A-0407 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. FIGURE 9: Thermostat Chart Unitary Products Group...
  • Page 12: Accessory Connections

    The twinning function of the board in this furnace ensures that both blowers turn on and off simultaneously, and operate on the same blower speed. Unitary Products Group...
  • Page 13: Single Stage Twinning Wiring Diagram

    The twinning func- tion of this board ensures that both blowers turn on and off simulta- neously, and operate on the same blower speed. Even when only one furnace is supplying heat, both furnace blowers must run. Unitary Products Group...
  • Page 14: Vent Termination 10 Ft. (3.0 M) Or Less

    THIS FURNACE IS NOT TO BE VENTED INTO AN FIGURE 16: Vent Termination UNLINED MASONRY CHIMNEY. Unitary Products Group...
  • Page 15: Typical Sidewall Vent Application

    IMPORTANT: The vent must be installed with the following minimum clearances as shown in Figure 19, and must comply with local codes OPTIONAL VENT SIDEWALL PIPE and requirements. VENT SYSTEM (field supplied) FURNACE FURNACE WATER TANK FIGURE 17: Typical Sidewall Vent Application Unitary Products Group...
  • Page 16: Home Layout

    A Termination should be positioned where vent vapors are not objec- properly sized duct from the outside to the furnace location must be pro- tionable. vided. Unitary Products Group...
  • Page 17: Combustion Airflow Path Through The Furnace Casing

    CHIMNEY OR OUTLET GAS VENT INLET ALTERNATE AIR INLET OPENING VENTILATION LOUVERS FOR UNHEATED CRAWL SPACE OPENING FIGURE 21: Alternate Air Intake, Air Outlet and Chimney Connections FIGURE 23: Typical Chimney Connections Unitary Products Group...
  • Page 18: Horizontal Air Inlet, Outlet And Chimney Connections

    Propane Installation Codes, the local building codes, furnace and vent vent connection (top right of unit) to the exterior of the building. Follow manufacturer's instructions. all notes, procedures and required materials in the SEALED COMBUS- Unitary Products Group...
  • Page 19: Safety Controls

    Too many supply or return registers closed or blocked off. reset controls that must be reset before operation can continue. The control module will lockout if the limit trips five (5) consecutive times. Control will reset and try again after one 1 hour. Unitary Products Group...
  • Page 20: Start-Up And Adjustments

    2 cubic ft. (0.0566 m .) of gas. has the following items: Calculate the furnace input by using one of the following equa- • 1 – 12” (30 cm) length x 1/8” (0.3 cm) diameter tubing tions. Unitary Products Group...
  • Page 21 If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifices with the gas orifices of the proper size for the type of gas you are using. Unitary Products Group...
  • Page 22: Gas Valve

    If adjustment is necessary, set to the following specifica- MANOMETER tions. After adjustment, check for gas leakage. Refer to Figure 27 for location of pressure regulator adjustment FIGURE 28: Reading Gas Pressure cap and adjustment screws on main gas valve. Unitary Products Group...
  • Page 23: Furnace Control Board

    This could be SLOW AMBER FLASH: Normal operation with call for heat. caused by a number of problems: faulty inducer, blocked vent pipe, bro- ken pressure switch hose or faulty pressure switch. Unitary Products Group...
  • Page 24: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    1501 - 1750 42.49 - 49.55 2452 0.15 0.03736 0.14 0.03487 0.30 0.07473 1751 - 2000 49.56 - 56.63 2542 0.19 0.04733 0.18 0.04484 0.30 0.07473 2001 & Above 56.64 - Above 2987 0.19 0.04733 0.18 0.04484 0.30 0.07473 Unitary Products Group...
  • Page 25: Blower Performance Cfm - (Without Filter)

    41.1 40.8 39.9 38.5 37.1 35.4 33.1 30.6 27.8 24.4 NOTES: 1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m /min). 2. Motor voltage at 115 V. † Indicates model available in LoNOx. Unitary Products Group...
  • Page 26: Field Installed Accessories - Non Electrical

    40, 60, 80 MBH HIGH ALTITUDE PRESSURE SWITCH KIT* (Does Not Include Orifices) 1PS0311 100, 115, 130 MBH 1CB0314 14-1/2” (”A”) CABINETS 1CB0317 17-1/2” (“B”) CABINETS COMBUSTIBLE FLOOR BASE FOR DOWNFLOW UNITS 1CB0321 21” (“C”) CABINETS 1CB0324 24-1/2” (“D”) CABINETS Unitary Products Group...
  • Page 27: Wiring Diagram

    268894-UIM-A-0407 SECTION X: WIRING DIAGRAM FIGURE 30: Wiring Diagram Unitary Products Group...
  • Page 28 NOTES Subject to change without notice. Printed in U.S.A. 268894-UIM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 167253-UIM-C-0706 Unitary 5005 Norman Product York Group Drive 73069...

This manual is also suitable for:

Gm8s*dhLm8s*dhLy8s*dh

Table of Contents