Unitary products group YMB Series Installation Manual

R-22 outdoor split-system heat pump models: 13 seer - ymb / hc3a / hl3a series 1.5 to 5 tons
Hide thumbs Also See for YMB Series:

Advertisement

Quick Links

INSTALLATION MANUAL
R-22
OUTDOOR SPLIT-SYSTEM
HEAT PUMP
MODELS: 13 SEER - YMB / HC3A / HL3A SERIES
1.5 TO 5 TONS
GENERAL 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATIONS REQUIRING TXV . . . . . . . . . . . . . . . . . . . . . . . . . . 5
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Oil Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Typical Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
R-22 Saturated Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
TEST Input Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Operational Mode Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Status Code Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
X/L Output Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Operational Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Sensor or Switch Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring Related Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences, or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
Certification applies only

TABLE OF CONTENTS

EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
LIST OF FIGURES
Demand Defrost Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Defrost Operation Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Hot Heat Pump Indoor Airflow Control . . . . . . . . . . . . . . . . . . . . . . . .14
Jumper Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
LIST OF TABLES
Air Handler Auxiliary Heat Functionality . . . . . . . . . . . . . . . . . . . . . . 16
Fossil Fuel Furnace Auxiliary Heat Functionality . . . . . . . . . . . . . . . 16
1-1/2 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . 18
2 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2-1/2 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . 18
3 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3-1/2 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . 19
4 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 Ton Subcooling Charging Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer, or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
R
P
LISTED
when the complete
system is listed
with ARI.
ISO 9001
Certified Quality
Management System
170761-UIM-B-0406

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YMB Series and is the answer not in the manual?

Questions and answers

Ira parker
March 3, 2025

Adjust aux coming on

User image 67c61aee19e80
1 comments:
Mr. Anderson
March 3, 2025

The auxiliary heat settings on the Unitary Products Group YMB Series can be adjusted based on the jumper position and outdoor ambient temperature. The system uses auxiliary heat when needed to satisfy thermostat demand. The LTCO (Low Temperature Cut-Off) setting is determined by the jumper position (-10 or ON). If the outdoor temperature falls below LTCO, the auxiliary heat engages immediately. The heat pump operation and auxiliary heat activation depend on temperature thresholds, as described in Table 10 of the manual.

This answer is automatically generated

Summary of Contents for Unitary products group YMB Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-22 OUTDOOR SPLIT-SYSTEM HEAT PUMP ISO 9001 LISTED MODELS: 13 SEER - YMB / HC3A / HL3A SERIES Certification applies only Certified Quality when the complete Management System system is listed 1.5 TO 5 TONS with ARI. TABLE OF CONTENTS GENERAL 1 .
  • Page 2: Unit Installation

    Check the directly on the ground. local weather bureau for the expected snow accumulation in your area. Isolate the unit from rain gutters to avoid any possible wash out of the foundation. Unitary Products Group...
  • Page 3: Oil Trap

    When the outdoor unit is above the indoor coil oil trapping is necessary. FIGURE 4: Underground Installation An oil trap should be provided for every 20 ft. of rise. See Figure 2. OUTDOOR COIL 10 In. 20 Ft. INDOOR 6 In. COIL 20 Ft. FIGURE 2: Oil Trap Unitary Products Group...
  • Page 4: Heat Protection

    Carefully remove the rubber plugs from the evaporator liquid and NOTE: Do not use the system refrigerant in the outdoor unit to purge or vapor connections at the indoor coil. leak test. Unitary Products Group...
  • Page 5: Installations Requiring Txv

    1/4” in the vapor line. Braze equalizer line on the inside surface of the unit service access panel and in Figure 14 making sure that tube opening is not brazed closed. of this instruction. Unitary Products Group...
  • Page 6: Typical Field Wiring

    For additional connection diagrams for all UPG equipment refer to “Low FIGURE 6: Typical Field Wiring Voltage System Wiring” document available online at www.upgnet.com FIELD CONNECTIONS CONTROL WIRING in the Product Catalog Section. Route low voltage wiring into bottom of control box as shown in Figure 5. Unitary Products Group...
  • Page 7: Cfm Selection Board

    The “TOTAL SYSTEM CHARGE” must be permanently stamped on the Check flare caps on service ports to be sure they are leak tight. DO unit data plate. NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum). Total system charge is determined as follows: Unitary Products Group...
  • Page 8: Heat Pump Flow Diagram

    VALVE SUCTION ACCUMULATOR COMPRESSOR (Cooling) FILTER DRYER (Solid core) LIQUID (Heating) SENSOR FIELD CONNECTED LINE COOLING CYCLE FLOW SHOWN IN COOLING POSITION. HEATING CYCLE FLOW FIGURE 8: Heat Pump Flow Diagram FIGURE 9: Demand Defrost Control Module Unitary Products Group...
  • Page 9: Test Input Functionality

    This is done each time power to the control is cycled. There- Air Conditioner fore, it is important that no loads be attached to the M1 or M2 terminals Single-Stage Compressor of the control. Incorrect system behavior could result. Reciprocating Two-Stage Compressor Scroll Two-Stage Compressor Unitary Products Group...
  • Page 10: Status Code Display

    Discharge line sensor failure (short) 2 (soft) Wiring, sensor or control setting related error 4 flashes Optional Bonnet Sensor Faults Bonnet sensor failure (short) Fossil Fuel Mode setting error (FFUEL jumper in OFF position but bonnet sensor present) Unitary Products Group...
  • Page 11: Wiring Related Fault Codes

    LAST ERROR pushbutton for one to five seconds. The control will flash both LED’s twice to indicate that no faults are stored in memory. Unitary Products Group...
  • Page 12: Defrost Operation

    LED’s. For instance, the X/L output will be energized with two flashes when defrost curve 2 is active. The control will lock out the com- pressor if the defrost curve selection jumper is not properly set. Unitary Products Group...
  • Page 13: Defrost Initiate Curves

    The location of the hot heat pump jumper is shown in Figures 10 and the outdoor ambient temperature is less than 50F, the indoor air- flow at the beginning of a heating cycle will always be low. Unitary Products Group...
  • Page 14: Hot Heat Pump Indoor Airflow Control

    Out will be energized regardless of the outdoor ambient temperature. pump application The two jumpers that do not affect the operation of this heat pump are Y2 LOCK and SWITCH POINT. Both of these jumpers apply only to two-stage compressor units. Unitary Products Group...
  • Page 15: Jumper Inputs

    (35F) and set the LTCO based on the jumper position (-10 or compressor back on even if the outdoor ambient temperature rises ON). above the LTCO setting during a call for heating. Table 10 describes the auxiliary heat operation for air handler mode. Unitary Products Group...
  • Page 16: Air Handler Auxiliary Heat Functionality

    The control will operate in fossil fuel mode instead of air handler mode so that the fur- nace and heat pump are not operated simultaneously. Unitary Products Group...
  • Page 17 The vapor line at the outdoor unit will feel warm to the touch. sense a second high-pressure switch opening before the six-hour timer The liquid line at the outdoor unit will feel cool to the touch. expires, the timer and counter will be reset. Unitary Products Group...
  • Page 18: Instructing The Owner

    253 (10) 256 (11) 259 (11) 270 (11) 271 (11) 274 (11) 277 (11) 288 (10) 289 (10) 292 (11) 295 (11) 305 (10) 307 (10) 310 (10) 313 (10) 323 (10) 325 (9) 328 (10) 331 (10) Unitary Products Group...
  • Page 19: Ton Subcooling Charging Chart

    307 (9) 309 (8) 313 (9) 324 (10) 326 (11) 324 (11) 326 (11) 323 (9) 326 (9) 328 (8) 331 (8) 344 (10) 345 (10) 343 (11) 346 (11) 341 (8) 345 (8) 347 (7) 350 (7) Unitary Products Group...
  • Page 20: Wiring Diagram

    SECTION X: WIRING DIAGRAM FIGURE 13: Wiring Diagram Subject to change without notice. Printed in U.S.A. 170761-UIM-B-0406 Copyright © by York International Corp. 2006. All rights reserved. Supersedes: 170761-UIM-A-0106 Unitary 5005 Norman Product York Group Drive 73069...