INSTALLATION
MANUAL
CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . .3
PRE-INSTALLATION INSPECTION OF
EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . 4
START-UP AND OPERATION . . . . . . . . . . . . . . . 10
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Complete Table of Contents on following pages.
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words:
NOTE, CAUTION, and WARNING. Notes are intended to
clarify or make the installation easier. Cautions are given
to prevent equipment damage. Warnings are given to
alert installer that personal injury and/or equipment dam-
age may result if installation procedure is not handled
properly.
CAUTION:
READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
INSTALLATION & OPERATING INSTRUCTIONS
FOR RP007 - 060 SERIES
WATER SOURCE HEAT PUMPS
RP007 TO 060
036-21521-001-A-0103

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RP007 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group RP007 Series

  • Page 1 INSTALLATION INSTALLATION & OPERATING INSTRUCTIONS FOR RP007 - 060 SERIES MANUAL WATER SOURCE HEAT PUMPS RP007 TO 060 CONTENTS INTRODUCTION ......3 PRE-INSTALLATION INSPECTION OF EQUIPMENT .
  • Page 2: Table Of Contents

    R-22 REFRIGERANT CHARGE ....12 HORIZONTAL MODELS - DIMENSIONS ..15 VERTICAL MODELS - DIMENSIONS ... . 16 Unitary Products Group...
  • Page 3: Product Nomenclature

    External high pressure and low pres- sure protection switches are included in each compressor circuit. Heat Pump models feature a pilot operated, sliding piston type, 4-way reversing valve with a replaceable magnetic solenoid coil. Unitary Products Group...
  • Page 4: Pre-Installation Inspection Of Equipment

    (if applicable) so that each unit will operate only in a single cooling or heating zone. In order to assure proper drainage of condensate, horizontal units can be slightly pitched in the same direction as drain pan outlet. Unitary Products Group...
  • Page 5: General Data

    3. Heating capacities are rated at entering air conditions of 68° F db / 59° F wb, 68° F entering water temperature. TABLE 2: OPERATING LIMITS - WATER LOOP APPLICATION COOLING HEATING Min. Entering Water 50°F 40°F Max. Entering Water 110°F 80°F Normal Entering Water 60-90°F 50-70°F Heating operation below 55°F requires insulated water circuit. Unitary Products Group...
  • Page 6: Clearances Required

    When the sound level is critical, it is recom- unit data label. Fuses must be of the time delay type. mended that both the supply and return Unitary Products Group...
  • Page 7: Room Thermostat And Control Wiring

    7.90 208-230/1/60 19.0 105.0 0.75 28.65 208-230/3/60 14.0 91.0 0.75 22.40 460/3/60 42.0 0.75 9.58 575/3/60 34.0 0.75 7.80 208-230/1/60 24.6 132.0 1.00 35.85 208-230/3/60 16.0 97.0 1.00 25.10 460/3/60 50.0 1.00 13.45 575/3/60 44.0 1.00 8.85 Unitary Products Group...
  • Page 8: Blower Performance

    1680 1660 1610 1540 Note: Units are shipped pre-wired for Medium speed. All airflow ratings are at lowest voltage rating of dual rating (i.e., 208 volt) Airflow ratings include resistance of wet coil and clean air filters. Unitary Products Group...
  • Page 9: Loop Water Supply And Piping Connections

    Damage due to erosion of the water temperature is constant and the flow rate can be water-to-refrigerant heat exchanger could occur. pre-set and turned on and off by some other means, such as a dedicated pump circuit or solenoid valve. Unitary Products Group...
  • Page 10: Condensate Drain Piping

    A room thermostat should be used to cycle the unit on soon as possible to minimize the loss of refrigerant. Do and off automatically as required to maintain the room not over-tighten. temperature at the set point of the thermostat. The air Unitary Products Group...
  • Page 11: Start-Up

    13. Check the unit for unusual vibrations, noises, mended (volts, amp draw, water temperature differ- leaks, etc. ences, etc.). A comparison of logged data with start-up and annual data is useful as an indicator of general equipment condition. Unitary Products Group...
  • Page 12: Refrigerant Charge

    2 lbs. – 6 oz. 1 lbs. – 12 oz. 1 lbs. – 14 oz. 1 lbs. – 6 oz. 1 lbs. – 7 oz. 0.75 1 lbs. – 1 oz. 1 lbs. – 1 oz. 0.50 10 oz. 10 oz. Unitary Products Group...
  • Page 13: Typical Single Phase Wiring Diagram

    036-21521-001-A-0103 APPLIES TO ALL 208/230-1-60 SINGLE PHASE MODELS Note: Solenoid Valve (SV) used on Heat Pump version only. FIGURE 2 : TYPICAL SINGLE PHASE WIRING DIAGRAM Unitary Products Group...
  • Page 14: Typical Three Phase Wiring Diagram

    036-21521-001-A-0103 APPLIES TO MODELS: RP030, RP036, RP048 & RP060 NOTE: Solenoid Valve (SV) used on Heat Pump version only. FIGURE 3 : TYPICAL THREE PHASE WIRING DIAGRAM Unitary Products Group...
  • Page 15: Horizontal Models - Dimensions

    20.00 45.75 25.50 2.25 25.00 1.00 18.00 6.50 9.19 10.31 5.88 58.00 25.00 20.00 55.75 27.50 2.25 38.99 1.00 18.00 6.00 12.25 11.38 5.13 63.00 25.00 20.00 60.75 27.50 2.25 42.00 1.00 18.00 6.00 12.25 11.38 5.13 Unitary Products Group...
  • Page 16: Vertical Models - Dimensions

    27.50 56.00 12.25 11.38 3.00 8.81 23.00 32.50 0.75 14.19 14.31 Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 2003. All rights reserved. Supersedes: Nothing 036-21521-001-A-0103 Unitary 5005 Norman Products York Group Drive 73069...