Unitary products group AHT8-UH Installation Manual

High efficiency tubular heat exchanger
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODEL: AHT8-UH
(Two Stage Upflow / Horizontal / LowNOx)
40 - 120 MBH INPUT
(11.72 - 35.17 kW) INPUT
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Horizontal Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Thermostat Chart - AC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Thermostat Chart - HP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Twinning Wiring Diagram - 1H/1C Thermostat . . . . . . . . . . . . . . . . . 15
Twinning Wiring Diagram - 2H/1C Thermostat . . . . . . . . . . . . . . . . . 15
Twinning Wiring Diagram - 2H/2C Thermostat . . . . . . . . . . . . . . . . . 15
Vent Termination 10 ft. (3.0 m) or less . . . . . . . . . . . . . . . . . . . . . . . . 15
Vent Termination more than 10 ft. (3.0 m) . . . . . . . . . . . . . . . . . . . . . 16
Minimum Duct Sizing For Proper Airflow . . . . . . . . . . . . . . . . . . . . . . . 5
Round Duct Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Recommended Filter Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal Manifold Pressure - Low Fire . . . . . . . . . . . . . . . . . . . . . . . . . 9
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . 10
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
LIST OF SECTIONS
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . .22
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
LIST OF FIGURES
Vent Termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Typical Sidewall Vent Application . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Home Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Casing to the Burner Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Air Inlet, Outlet and Chimney Connections . . . . . . . . . . . . . . . . . . . . .19
Typical Chimney Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . .20
Pressure Switch Tubing Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
LIST OF TABLES
Roof Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Unconfined Space Minimum Area in Square Inch . . . . . . . . . . . . . . .20
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Field Installed Accessories - Non Electrical . . . . . . . . . . . . . . . . . . . .27
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
This product must be installed in strict compliance with the installa-
tion instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical
codes.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
272312-UIM-A-0407

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AHT8-UH and is the answer not in the manual?

Questions and answers

Summary of Contents for Unitary products group AHT8-UH

  • Page 1: Table Of Contents

    INSTALLATION MANUAL HIGH EFFICIENCY EFFICIENCY RATING CERTIFIED TUBULAR HEAT EXCHANGER SERIES MODEL: AHT8-UH ISO 9001 Certified Quality (Two Stage Upflow / Horizontal / LowNOx) Management System 40 - 120 MBH INPUT (11.72 - 35.17 kW) INPUT LIST OF SECTIONS SAFETY ..........1 VENT SYSTEM .
  • Page 2: Safety

    When outdoor air is used for combustion, the combustion air intake duct of standard ANSI Z21-47 • CSA 2.3. system termination must be located external to the building and in an area where there will be no exposure to the substances listed above. Unitary Products Group...
  • Page 3 248 CMR 5.08(2)(a)1 through 4. Unitary Products Group...
  • Page 4: Ductwork

    In this example, the duct system attached to the plenum has a sufficient area so that the furnace operates at the specified external static pres- sure and within the air temperature rise specified on the nameplate, providing the return duct is properly sized as well. Unitary Products Group...
  • Page 5: Minimum Duct Sizing For Proper Airflow

    To properly design the ductwork for the building, refer to the ASHRAE Fundamentals Handbook, Chapter on “DUCT DESIGN” or a company that specializes in Residential and Modular Home duct designs. Unitary Products Group...
  • Page 6: Dimensions

    Lay the furnace on its back. IMPORTANT: This furnace may be installed in a horizontal position on Remove the screws from the toe plate. either side as shown above. It must not be installed on its back. Remove the toe plate. Unitary Products Group...
  • Page 7: Typical Attic Installation

    “INSTALLATION IN FREEZING TEMPERATURES” in Section I IMPORTANT: if an external mounted filter rack is being used see the instructions provided with that accessory for proper hole cut size. Unitary Products Group...
  • Page 8: Filters

    300 feet per minute (91 m/min). All velocities over this require the use of high velocity filters. Refer to Table 15. GROUNDED JOINT UNION All installations must have a filter installed. DRIP MAY BE INSTALLED INSIDE OR OUTSIDE UNIT. FIGURE 6: Upflow Gas Piping Unitary Products Group...
  • Page 9: Horizontal Gas Piping

    0.42 0.42 0.42 31.7 0.42 0.42 0.42 33.5 0.42 0.42 0.42 35.4 0.42 0.42 0.38 1000 37.3 0.41 0.37 0.34 1050 39.1 0.37 0.34 0.31 1100 41.0 0.34 0.31 0.28 2500 (LP) 93.2 (LP) 1.03 0.95 0.87 Unitary Products Group...
  • Page 10: Electrical Power

    3. Wire size based on copper conductors, 60º C, 3% voltage drop. "Unit Amps" refers to the full load current. 4. Min wire size (awg) @ 75 ft. one way refers to the minimum recommended field installed wire size. Unitary Products Group...
  • Page 11: Electrical Wiring

    (HOT) in the Product Catalog Section. BLK/BLK HUM (HOT) WHT/WHT GRN/GRN EAC (HOT) WIRING INSIDE JUNCTION BOX BURNER JUNCTION COMPARTMENT DOOR SWITCH CLASS 2 SYSTEM CONTROL WIRING BLOWER TO THERMOSTAT COMPARTMENT IGNITION MODULE FIGURE 8: Electrical Wiring Unitary Products Group...
  • Page 12: Thermostat Chart - Ac

    272312-UIM-A-0407 FIGURE 9: Thermostat Chart - AC Unitary Products Group...
  • Page 13: Thermostat Chart - Hp

    272312-UIM-A-0407 FIGURE 10: Thermostat Chart - HP Unitary Products Group...
  • Page 14: Accessory Connections

    Figure 12. Place the "W2 way, it must not be used. Delay" jumper in the same position of both furnace control boards. If the jumper is left in the "OFF" position, the furnaces will operate only at low fire. Unitary Products Group...
  • Page 15: Twinning Wiring Diagram - 1H/1C Thermostat

    FROM RIDGE, WALL, TWIN TWIN OR PARAPET W/W1 W/W1 CHIMNEY W2 RELAY FIGURE 15: Vent Termination 10 ft. (3.0 m) or less FURNACE 1 FURNACE 2 TWO-STAGE 2H/2C THERMOSTAT FIGURE 14: Twinning Wiring Diagram - 2H/2C Thermostat Unitary Products Group...
  • Page 16: Vent Termination More Than 10 Ft. (3.0 M)

    60 degree offset is permitted. The vent system must be attached to the flue collar with a minimum of two (2) mechanical fasteners, such as screws or rivets. See Figure 21. FIGURE 17: Vent Termination Unitary Products Group...
  • Page 17: Typical Sidewall Vent Application

    IMPORTANT: The vent must be installed with the following minimum minimum length of 4.5 feet (1.37 m) and a maximum length of 34.5 feet clearances as shown in Figure 20, and must comply with local codes (10.82 m) with up to 4 elbows. and requirements. Unitary Products Group...
  • Page 18: Home Layout

    The vent system may be supported by the use of clamps or hangers secured to a permanent part of the structure every 4 ft. (1.22 m). Unitary Products Group...
  • Page 19: Combustion Airflow Path Through The Furnace Casing To The Burner Box

    A manually operated damper or manually adjustable louvers are not permitted for use. A automatically operated damper or automatically adjustable lou- vers shall be interlocked so that the main burner cannot operate unless either the damper or the louver is in the fully open position. Unitary Products Group...
  • Page 20: Typical Chimney Connections

    4. The blocking effects of louvers, grilles and screens must be given INLET AIR (b) consideration in calculating free area. If the free area of a specific AIR (a) louver aor grille is not known. FIGURE 26: Outside and Ambient Combustion Air Unitary Products Group...
  • Page 21: Safety Controls

    The operation of this control indicates a malfunction in the combustion air blower, heat exchanger or a blocked vent pipe connection. Corrective action is required. These are manual reset controls that must be reset before operation can continue. Unitary Products Group...
  • Page 22: Start-Up And Adjustments

    2 cubic ft. (0.0566 m .) of gas. to connect the U-tube manometer or the digital pressure measur- Calculate the furnace input by using one of the following equa- ing equipment to the gas valve pressure ports. tions. Unitary Products Group...
  • Page 23 If the actual input is significantly higher than the furnace input specified on the rating plate then replace the gas orifices with the gas orifices of the proper size for the type of gas you are using. Unitary Products Group...
  • Page 24: Gas Valve

    If adjustment is necessary, set to the following ASSEMBLY PRESSURE specifications. After adjustment, check for gas leakage. U-TUBE SHOWN MANOMETER Refer to Figure 28 for location of pressure regulator adjustment cap and adjustment screws on main gas valve. FIGURE 29: Reading Gas Pressure Unitary Products Group...
  • Page 25: Furnace Control Board

    SLOW AMBER FLASH: Normal operation with call for heat. module is ON. RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check The manual shut-off valves in the gas line to the furnace must be twinning wiring. open. Unitary Products Group...
  • Page 26 12 RED FLASHES: This code indicates an open igniter circuit, which could be caused by a disconnected or loose wire or by a cracked or bro- ken igniter. Unitary Products Group...
  • Page 27: Filter Performance - Pressure Drop Inches W.c. And (Kpa)

    1BR0221 BOTTOM RETURN FILTER KIT 1-4” FILTER 21” CABINETS 1BR0124 BOTTOM RETURN FILTER KIT 1” FILTER 24-1/2” CABINETS 1BR0224 BOTTOM RETURN FILTER KIT 1-4” FILTER 24-1/2” CABINETS 1HF0801 INTERNAL FILTER KIT WITH 1” FIBER FILTER ALL MODELS Unitary Products Group...
  • Page 28: Blower Performance Cfm - Upflow (Without Filter) - Bottom Return

    1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m /min). 2. Motor voltage at 115 V. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 29: Blower Performance Cfm - Upflow (Without Filter) - Left Side Return

    3. Motor voltage at 115 V. 4. Airflow through motor side return (right side) maybe slightly less than shown above. * Input / CFM / Cabinet Width (A=14-1/2, B=17-1/2, C=21, D=24-1/2) † Indicates model available in LoNOx. Unitary Products Group...
  • Page 30: Wiring Diagram

    272312-UIM-A-0407 SECTION IX: WIRING DIAGRAM FIGURE 31: Wiring Diagram Unitary Products Group...
  • Page 31 272312-UIM-A-0407 NOTES Unitary Products Group...
  • Page 32 Subject to change without notice. Printed in U.S.A. 272312-UIM-A-0407 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 167185-UIM-C-0806 Unitary 5005 Norman Product York Group Drive 73069...