P R O D U C T I D E N T I . I E R 1 8 0 = 1 5 T o n 2 4 0 = 2 0 T o n E H = I n d o o r U n i t FIGURE 1 - PRODUCT NOMENCLATURE Unitary Products Group...
The clearances listed on unit dimensions drawing (Pages 18 and 19) are required for the proper service and operation of the unit. Before rigging any unit, determine its weight from Table Unitary Products Group...
Ambient Air on Indoor Coil (Heating Cycle) - °F Rated in accordance with ARI Standard 110, utilization range “A”. Below 0ºF the control circuit will lock out the compressor and allow the electric heat accessory to cycle at its stand by capacity. Unitary Products Group...
Suspension accessories can be applied on arrangement (c). HORIZONTAL POSITION FIGURE 4 - VERTICAL AND HORIZONTAL APPLICATIONS VERTICAL/HORIZONTAL INSTALLATION These indoor units are shipped for vertical installation with vertical air discharge as shown in Figure 4 on page 8. Unitary Products Group...
1-23/32 inch knockout in the top panel of the basic unit. FIGURE 5 - ELECTRIC HEAT ACCESSORY TABLE 5: ELECTRIC HEATER DIMENSIONS FEH180 & 240 Heater Heater Dimensions (inches) Nom.
The line should be for the matching outdoor unit for piping limitations, line insulated where moisture drippage will be objection- sizes and other design considerations. able or cause damage to the area. Unitary Products Group...
After the movable flange has been rotated to the that this balancing be done by someone other than the proper number of “turns open”, the set screw should be equipment installer. tightened against the flat on the barrel to lock the mov- Unitary Products Group...
4. Knowing the pressure drop across a dry coil the 4800 5600 6400 7200 8000 8800 9600 actual CFM through the unit can be determined SUPPLY AIR CFM from the curve in Figure 16. FIGURE 16 - CFM VS PRESSURE DROP Unitary Products Group...
Based on three, 75 C insulated copper conductors in conduit and ambient of 30 C. Based on a 5% voltage drop, since unit controls are powered off the unit supply. Two minute time delay between system 1 and system 2. Unitary Products Group...
Based on three 75 C insulated copper conductors in conduit and ambient of 30 C Based on a 5% voltage drop, since unit controls are powered off the unit supply. Two minute time delay between system 1 and system 2. Unitary Products Group...
The filters must be replaced as often as necessary to Maintain belt tension to extend belt life. Replace the assure good air flow and filtering action. Clean filters signs of failure begin to appear. will prevent any loss in capacity and efficiency. Unitary Products Group...
*Refer to INSTALLING REFRIGERANT MAINS in installation instruction when piping through the opposite side of the unit. 2-7/8 Ø 1-3/8 2-7/8 FIGURE 17 - UNIT DIMENSIONS FEH180 TABLE 12: FEH180/240 MINIMUM CLEARANCES Side with RETURN AIR opening 24” Side with SUPPLY AIR opening 24”...
035-16626-000-E-0103 FIGURE 18 - UNIT DIMENSIONS FEH240 Clearances for FEH240 • 24” on one side for piping connection and access to blower motor • 1” on opposite sides and rear Unitary Products Group...