MAINTENANCE ......18 See the following page for a complete Table of Contents. MODEL: FF-10 NOTES, CAUTIONS AND WARNINGS Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING.
S = 208/230-460-3-60 Factory Options A = None Special Options AA = None Generation 1 = First Generation 2 = Second Generation Product Style A = Style A B = Style B *NOT AVAILABLE IN HEAT PUMP Unitary Products Group...
As soon as a unit is received, it should be inspected for possi- ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing. Unitary Products Group...
IR ON NDOOR EATING YCLE Rated in accordance with ARI Standard 110, utilization range “A”. Below 0ºF the control circuit will lock out the compressor and allow the electric heat accessory to cycle at its stand by capacity. Unitary Products Group...
4. Attach the blower section to the coil section with the machine bolts removed in Step 2. The FF-10 unit is shipped for vertical installation with a vertical air discharge as shown in Figure 2, but may be 5. Before replacing the panel, see Duct Connection converted to other arrangements per the following and Drain Connection.
It is provided with a squeeze connector for securing the wiring harness, and its location corresponds to the loca- tion of the 1-23/32 inch knockout in the top panel of the basic unit. FIGURE 4 - ELECTRIC HEAT ACCESSORY Unitary Products Group...
2 - 1 / 2 K N O C K O U T F O R P O W E R W I R I N G W H E N E L E C T R I C H E A T E R I S U S E D FIGURE 5 - RETURN AIR GRILLE FF-10 FIGURE 7 - SUPPLY AIR PLENUM FF-10 Electric Heaters are NOT UL approved for installation within a SUPPLY AIR PLENUM.
The liquid and suction connections must be piped outside the used, care should be taken to avoid sharp bends which may unit. Refer to the unit drawing for locations and the dimen- cause a restriction. sions of these connections. Unitary Products Group...
(along unit. with the grommets) onto the refrigerant lines. After the brazed joints have cooled, slide the panel back into place and secure TABLE 5: ELECTRICAL DATA - FF-10 it to the unit frame. Max. Fuse Blower...
#19 Solid the wiring diagram inside the motor terminal box #18 Solid when reconnecting motor leads for a 208 or 230 volt #18 Stranded #16 Stranded power supply. #14 Stranded #12 Stranded 035-16602-001 FIGURE 10 -TYPICAL FIELD WIRING Unitary Products Group...
DRIVE RANGE TURNS activated while the test is being run. OPEN 550-730 RPM Knowing the pressure drop across a dry coil the actual CFM through the unit can be determined from the curve in Figure 13. Unitary Products Group...
If the CFM is above or below the specified value, the supply air motor pulley may have to be re-adjusted. After one hour of FF-10 0.25 0.15 0.05 1500 2500 3500 4500 5500 6500 FIGURE 13 -CFM VS PRESSURE DROP Unitary Products Group...
FF-10 550-730 2.8-3.8 56.3 These factory-mounted motors are wired for a 460V power supply. Refer to the wiring diagram inside the motor terminal box when reconnecting the motor leads to a 208 or 230 volt power supply. Unitary Products Group...
The filters must be replaced as often as necessary to assure Maintain belt tension to extend belt life. Replace the signs if good air flow and filtering action. Clean filters will prevent any failure begins to appear. loss in capacity and efficiency. Unitary Products Group...