Filter Hood Or Dry Grease Extractor - Spring Air Systems KES Enviro Operation And Maintenance Manual

Table of Contents

Advertisement

E X H A U S T D I S C H A R G E
D U C T W O R K
T O K E S F F A N U N I T
Remote wiring of KES Enviro units with Water Wash Hood and Panel
Filter Hood or Dry Grease Extractor: RPD10 Remote Panel
The KES unit off/on operation is controlled from RPD10 remote annunciation panel. The fan selector switch
on the RPD10 remote panel closes and sends power through terminals 5 & 4 to the LV10 J-Box to energize
the exhaust fan circuit. (The LV10 J -Box is mounted on the KES-ISH filter section). The "NORMAL"
operation pilot on the RPD10 remote kitchen annunciation panel energizes and after 30 seconds the KES
control circuit within the RPD10 remote panel is activated. The exhaust fan motor is energized through the
terminals 5 & 4 to the motor starter. See figure 8 for the RPD10 remote panel wiring and figure 9 for
dimensions.
RPD10A ELECTRICAL DATA
15 AMP CURCUIT BREAKER
FAN SWITCH
OFF/ON
OVERIDE SWITCH
L
N
I1
I2
I3
I4
I 5 I 6
I7
I8
L
N
I 1 I 2 I 3 I 4
AUX!
Mo 09:00
RUN/STOP
01. 20. 03
LOGO!
ESC
OK
Q 1
Q2
1
2
1
Q1
Q2
Q3
Q4
Q 3
Q4
1
2
1
2
1
2
1
2
1
2
1
K E S F
F I E L D I N T E R C O N N E C T I N G
D U C T W O R K A S R E Q U I R E D
I N T E R L O C K B E T W E E N K E S - I S H L V 1 0 A N D K E S F M O T O R S T A R T E R
P O W E R S U P P L Y
T H R E E ( 3 ) W I R E S T O
R P W 1 0 P A N E L F R O M
W A T E R W A S H P A N E L
P O W E R S U P P L Y
T O S B 1 0 W A S H P A N E L
Figure 8
2
TWO (2) WIRES TO THE WET CHEMICAL
2
C O N T R O L H E A D , 1 2 0 V / 1 / 6 0 - 1 A M P
RPD10 Wiring Schematic
Figure 9
Enviro Maintenance Manual 2004
K E S - I S H
P O W E R S U P P L Y
T O R P D 1 0 R E M O T E
1 2 0 V / 1 / 6 0
T E N ( 1 0 ) W I R E S F R O M
T H E R P W 1 0 C O N T R O L L E R
F R O M T H E K E S - I S H L V 1 0
J - B O X - 1 2 0 V / 1 / 6 0
W A T E R W A S H
P A N E L M O D E L
S B 1 0 C O R S B 1 0 H
POWER SUPPLY TO THE KES UNIT
RPD10 CONTROL PANEL - 120V/1/60 - 15 AMPS
OPTIONAL BMS START/STOP - 120V/1/60
CLOSE CONTACT ACROSS 20&21 TO START UNIT
OPEN CONTACT ACROSS 20&21 TO STOP UNIT
JUMPER MUST BE IN PLACE AS NOTED TO OPERATE FROM BMS
TO KES UNIT LV10 PANEL ON FILTER
B O X - T E N ( 1 0 ) W I R E S
1 2 0 V / 1 / 6 0 - 1 0 A M P S .
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
MOTOR STARTER, 120V/1/60 - 2 AMPS
(OPTIONAL) THREE (3) WIRES TO
MOTORIZED INLET DAMPER AND END
S W I T C H , 1 2 0 V / 1 / 6 0 - 1 A M P
DRY CONTACT FOR BUILDING FIRE ALARM
FIRE ANUNCIATION, 5 AMPS MAXIMUM, N/O
E X H A U S T I N L E T
D U C T W O R K
R P W 1 0
C O N T R O L L E R
P O W E R W I R I N G B Y G E N E R A L C O N T R A C T O R
C O N T R O L W I R I N G B Y M E C H A N I C A L C O N T A C T O R
F A C T O R Y W I R I N G B Y S P R I N G A I R S Y S T E M S
LEGEND
TERMINAL
D E S C R I P T I O N
1&4
P O W E R S U P P L Y F R O M B R E A K E R P A N E L
5
KES FAN/NORMAL OPERATION
12
P R E F I L T E R C L O G G E D
13
B A G F I L T E R C L O G G E D
14
B O X F I L T E R C L O G G E D
15
F I L T E R O U T / L O W A I R
16
FIRESTAT - HIGH LIMIT
17
0 D O R S P R A Y U N I T
18
LV10 RESET
2 0 & 2 1
BMS START/STOP
PANEL MOUNTING
H O L E S L O C A T E D
I N P A N E L B A C K .
K E S
8.0"
OFF/ON
FILTER
O V E R I D E
WARNING
N O R M A L
FIRE
PREFILTER
BOX FILTER
C L O G G E D
CLOGGED
FILTER
BAG FILTER
C L O G G E D
REMOVED
RPD10 DIMENSIONAL DATA
5 "
1 4 . 0 "