E1200I Ac System Power Requirements; E1200I Dc Chassis Physical Design; E1200I Dc System Power Requirements - Dell E1200i ExaScale Installation Manual

Hide thumbs Also See for E1200i ExaScale:
Table of Contents

Advertisement

E1200i AC System Power Requirements

Parameter
Nominal Input Voltage
Maximum Power Consumption
Maximum Thermal Output (5,700 W)
Maximum Input Current (per power supply)
Maximum System Power Input

E1200i DC Chassis Physical Design

Parameter
Height
Width
Depth (without cable management system)
Chassis weight with factory-installed components (backplane
and air filter)
Weight fully loaded (backplane, air filter, 2 fan trays, 10
SFM3s, RPMs, and 14 line cards)
Mounting
Rack clearance required
Thermal Output
Maximum (fully-loaded chassis with 10-port 10GE line cards) 16,446 BTU/hr
Minimum (chassis with one 10-port 10GE line card)

E1200i DC System Power Requirements

Parameter
Nominal Input Voltage
Maximum Power Consumption
Maximum Thermal Output (5,100 W)
Maximum Input Current (per DC PEM)
82
|
System Specifications
Specifications
200-240 VAC 50/60 Hz
6,634 Watts
19,449 BTU/hour
15.0 A @ 200 VAC
12.5 A @ 240 VAC
6.0 KVA @ 200/240 VAC
Specifications
36.75 inches (93.35 cm)
17.40 inches (44.20 cm)
21.25 inches (53.98 cm)
97 pounds (approx.) (44.00 kg)
319 pounds (approx.) (144.70 kg)
Attached rack mount brackets are factory set for front
mounting in a standard 19-inch rack.
Mounting brackets are adjustable for center and rear
mounting.
Optional brackets are available for front or center mounting
in a 23-inch rack or cabinet.
Front: 18 inches
Rear: 20 inches
1,997 BTU/hr
Specifications
-44 to -60 VDC
5,400 W
17,402 BTU/hour
150 A

Advertisement

Table of Contents
loading

Table of Contents