Input Current Control - Daikin SiENBE07-618_C Service Manual

C-series inverter pair duct connected type
Table of Contents

Advertisement

Control Specification
3.5

Input Current Control

Outline
The microcomputer calculates the input current during the compressor is running, and sets the
frequency upper limit from the input current.
In case of heat pump model, this control which is the upper limit control of the frequency takes
priority to the lower limit of control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
Š After 2.5 seconds in this zone, the compressor is stopped.
Drooping zone
Š The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
Š After this, the output frequency is pulled down by 2 Hz every second until it reaches the keep
Keep zone
Š The present maximum frequency goes on.
Reset zone
Š Limit of the frequency is canceled.
Limitation of current drooping and stop value according to the outdoor temperature
Š The current droops when outdoor temperature becomes higher than a certain level
34
zone.
50 class
Cooling
(A)
20.0
(A)
10.0
(A)
9.0
(depending on the model).
Compressor Stop
60 class
Heating
Cooling
20.0
15.0
12.0
14.0
11.0
SiENBE07-618_C
Stop Zone
Drooping Zone
Keep Zone
Reset Zone
(R4304)
Heating
16.0
15.0
Function and Control

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents