4. REFRIGERANT FLOW DIAGRAM

Indoor Unit
AWR222CLE
Indoor Unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a proper
insulation material. The thickness of the insulation should be a
min. 8 mm.
CAUTION
Wide tube
O.D.
ø15.88 mm
(5/8 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit
AER222SC
AER222SC3
Outdoor Unit
Wide tube
service
valve
Muffler
Capillary for
liquid injection
Narrow
tube
service
valve
Capillary tube
Check port
Thickness:
Min. 8 mm
10
Compressor
Accumulator
Drier
Insulation
Wide tube
Thickness:
Min. 8 mm
Narrow tube