Refrigerant Flow Diagram - Argo FCR518CL Technical & Service Manual

Table of Contents

Advertisement

4. REFRIGERANT FLOW DIAGRAM

Indoor Unit
AWR518CL
FCR518CL
Indoor Unit
AWR522CL
FCR522CL
Indoor Unit
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
Outdoor Unit
Indoor Unit
Outdoor Unit
Wide tube
service
valve
Wide tube
O.D.
ø15.88 mm
(5/8 ")
Narrow
tube
service
Narrow tube
valve
O.D.
ø6.35 mm
(1/4")
Check port
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
AER518SC3
Outdoor Unit
AER522SC3
Outdoor Unit
Compressor
Muffler
Accumulator
Capillary for
liquid injection
Capillary tube
Strainer
Thickness:
Min. 8 mm
26
Insulation
Wide tube
Thickness:
Min. 8 mm
Narrow tube